Gas Conversions; Lp Gas Conversion - KitchenAid KDRS407VSS Instructions D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

IMPORTANT: Gas conversions from Natural gas to LP gas must
be done by a qualified installer.
WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to LP, have a qualified person make sure
gas pressure does not exceed 14" (36 cm) water
column.
Examples of a qualified person include:
licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.

LP Gas Conversion

WARNING
Tip Over Hazard
A child or adult can tip the range and be killed.
Connect anti-tip bracket to rear range foot.
Reconnect the anti-tip bracket, if the range is moved.
Failure to follow these instructions can result in death
or serious burns to children and adults.
1. Turn the manual shutoff valve to the closed position.
2. Unplug range or disconnect power.
A
A. To range
B. Shutoff valve (closed position)
C. Gas supply line
20

GAS CONVERSIONS

1. Remove the access cap by using a wrench, turning the
2. Remove spring retainer from the cap by pushing against the
3. Test the gas pressure regulator and gas supply line.
B
1. If installed, remove the burner grates.
C
2. Remove burner cap.
3. Remove the burner head.
To Convert Gas Pressure Regulator
access cap counterclockwise.
flat side of the spring retainer. Look at the spring retainer to
locate the "NAT" or "LP" position. Turn over the spring
retainer so the "LP" is showing on the bottom. Snap the
spring retainer back into the cap. Reinstall the cap onto the
regulator.
E
D
A. Access cap
B. Gasket
C. Gas pressure regulator
The regulator must be checked at a minimum 1" (2.5 cm)
water column above the set pressure. The inlet pressure to
the regulator should be as follows for operation and checking
the regulator setting:
LP Gas:
Minimum pressure 11" (27.9 cm) WCP
Maximum pressure 14" (35.5 cm) WCP.
Gas Supply Pressure Testing
Gas supply pressure for testing regulator must be at least
1" water column pressure above the manifold pressure
shown on the model/serial rating plate.
Line pressure testing above ½ psi gauge (14" WCP)
The range and its individual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of
½ psi (3.5 kPa).
Line pressure testing at ½ psi gauge (14" WCP) or lower
The range must be isolated from the gas supply piping
system by closing its individual manual shutoff valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than ½ psi (3.5 kPa).
To Convert Surface Burners
NOTE: A ⁷⁄₈" socket must be used to remove the burner head
of the large dual burners.
A
B
C
D. LP position
E. NAT position

Publicité

Table des Matières
loading

Table des Matières