CONNECTOR DESCRIPTIONS

230VAC
GB
CONNECTOR DESCRIPTIONS
To avoid damages to electronic components caused by the PCB bending, do not press too much while fixing the
terminal block.
DESCRIPTION
Lh
N
230VAC
Lc
V+
16 VDC
M
0V (Common)
U
2-10VDC
Feedback output signal**
M
0V (Common)
Y
0-10VDC***
Modulating control signal
M
0V (Common)
Y1
Y2
*Connect (Lh+N) in modulating control mode; Connect (Lh+N) to"open" or (Lc+N) to "close" in 3-point floating control mode.
**Only available in modulating control mode.
*** See Chapter 5 and DIP switch 4−6 for available modulating control signal types.
Connect the ground terminal to the proper screw labelled with the ground symbol as shown in picture (A)
SE
FÖRKLARING ANSLUTNINGAR
Tryck ej för hårt när kabelkontakten kontakteras för att undvika skador på kretskortet till följd av böjning.
FÖRKLARING
Lh
N
230VAC
Lc
V+
16 VDC
M
0V (Gemensam)
U
2-10VDC
M
0V (Gemensam)
Y
0-10VDC***
Modulerande styrsignal
M
0V (Gemensam)
Y1
Y2
*Anslut (Lh+N) vid modulerande styrning. Anslut (Lh+N) för att "öppna" eller (Lc+N) för att "stänga" in 3-punkts styrning.
**Endast tillgänglig med modulerande styrning.
*** Se kapitel 5 och DIP brytare 4-6 för tillgängliga typer av modulerande styrsignaler.
Anslut jordledaren med skruven som är märkt med jordsymbolen enligt bild (A)
8
A
FUNCTION
Power supply*
Voltage output
(Max load 25mA)
(Max load 2mA)
Not to be used
FUNKTION
Strömförsörjning*
Spänningsutgång
(Max last 25mA)
Återföringssignal**
(Max last 2mA)
Skall inte användas
ground terminal
MIN WIRE AREA
1,5mm2
0.5 mm2
0.5 mm2
0.5 mm2
MIN KABEL AREA
1,5mm2
0.5 mm2
0.5 mm2
0.5 mm2
MAX WIRE LENGTH
75 m
200 m
200 m
200 m
MAX KABEL LÄNGD
75 m
200 m
200 m
200 m