Phoenix Inverter
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25°C (VA)
Cont. output power at 25°C (W)
Cont. output power at 40°C (W)
Cont. output power at 65°C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
GENERAL
Programmable relay
(4)
Protection
(2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connection
Weight (kg)
Dimensions (hxwxd)
STANDARDS
Safety
Emission / Immunity
1) Can be adjusted to 60Hz; 120V/60Hz on request
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) Multipurpose relay which can be set for general alarm, DC undervoltage or genset start signal
function
20
Output voltage: 230 VAC ± 2%
(3)
Operating temp.: -40 to +65°C (fan assisted cooling)
Humidity (non-condensing): max 95%
Material & Colour: aluminium (blue RAL 5012) Protection: IP 21
M8 bolts (2 plus and 2 minus connections)
EN 55014-1, EN 61000-3-2 / EN 55014-2, EN 61000-3-3
24/5000
19 – 33
Frequency
5000
4000
3700
3000
10000
94
30
Yes
a - g
Screw clamp 13mm² (6 AWG)
30
444 x 328 x 240
EN 60335-1, EN 60335-2-29
48/5000
38 – 66
50 Hz ± 0,1%
:
5000
4000
3700
3000
10000
95
30
Yes