s Never connect the power cable to the terminal board for control
cables. (Otherwise it may be broken.)
s Be sure to wire between the control wire terminal boards for
indoor unit, outdoor unit and BC controller.
Transmission cables are of crossover wiring method by non-polarized
2-wires.
Use 2-core shielding cables (CVVS, CPEVS) of more than 1.25mm
diameter for transmission cables.
The switch capacity of the main power to BC controllers and the wire
size are as follows:

6. Setting addresses and operating units

The address switch of each BC controller is set to "000" when shipped
from the factory. Check it.
Set the address switch to 1 + the address of the outdoor unit.
s The BC controller address should generally be set to 1 + the
address of the outdoor unit. However, if this would result in it
having the same address as another outdoor unit, set the ad-
dress between 51 and 100, making sure that it is different from
the address of other controllers.
Please refer to the outdoor unit installation manual.

7. Test run

Before getting test run checked
s After installing, piping and wiring the indoor units and BC con-
trollers, check to see again that there is no refrigerant leakage
or no slack on power and control cables.
s Use a 500V megger to check that there is an insulation resist-
ance of more than 1.0MΩ between the power terminal bed and
the ground. If it is less than 1.0MΩ, do not get operated.
Caution:
Never measure the insulation resistance of the terminal bed for
control cables.
12
Switch (A)
Capacity
Fuse
15
15
For other detailed information, refer to the outdoor unit installation
manual.
2
in
Caution:
Do not use anything other than the correct capacity fuse and
breaker. Using fuse, conductor or copper wire with too large ca-
pacity may cause a risk of malfunction or fire.
Ensure that the outdoor units are put to the ground. Do not con-
nect the earth cable to any gas pipe, water pipe, lightening rod or
telephone earth cable. Incomplete grounding may cause a risk of
electric shock.
Wire size
Molded case
Earth leak-
circuit breaker
age breaker
20A
20A 30mA
1.6mm
0.1 s or less