2. Selecting an installation site

2.1. Installation site

Place not exposed to rain (BC controller is a special machine for
indoor use.)
Place with large enough service space
Place in which refrigerant pipes can be provided within the limita-
tions
Place not exposed to direct radiant heat from other heat sources
Do not install the unit in any oily steamy place or near any machine
that generates high frequencies. Doing so may cause a risk of fire,
erroneous operation or dew drop.
Place with less noise effect generated from other units
Place in which water piping, refrigerant piping and electrical wiring
can be done easily
Avoid places exposed to the generation, inflow, accumulation or leak-
age of flammable and sulfuric gases
Place in which a downward pitch of more than 1/100 can be taken for
drain piping
1. For hanging from the ceiling
Provide a inspection hole 450 mm square to the ceiling surface as
shown in 2.2.1 1.
Above the ceiling of corridor, bath room, etc., where persons are not
regularly there
(Avoid installing at around center of the room.)
Place with strength to the degree that hanging bolts can be mounted
(that sustains a pull-out load of 60kg per bolt)
Be sure to install BC controllers at level.
2. For stacking on a rack
Place in which sufficient space can be obtained around a rack
Place with floor strength that sustains the entire weight
Warning:
Be sure to install the unit in a place that well sustains the entire
weight.
If there is a lack of strength, it may cause the unit to fall down,
resulting in an injury.
Caution:
Be sure to install the unit at level.
2.2. Securing installation and service
space
1. For hanging from the ceiling
(This is a reference view showing the least installation space.)
<Top view>
A
C
B
300
A Inspection hole
B On the side of outdoor unit piping
C Control box
D On the side of indoor unit piping
213
D
A
200
5