Safety Information; Installation - Tuthill Fill-Rite 700V Serie Manuel D'installation, Fonctionnement Et Securite

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Safety Information

WARNING! Electrical wiring should be performed ONLY by a licensed
electrician in compliance with local, state, and national electrical code
NEC/ANSI/NFPA 70, NFPA30, and NFPA 30A, as appropriate to the intended
use of the pump. Threaded rigid conduit, sealed fittings, and conductor seal
should be used. The pump must be properly grounded. Improper installation or
use of this pump can result in serious bodily injury, or death!
WARNING! To insure safe and proper operation of your equipment, it is critical
to read and adhere to all of the following safety warnings and precautions.
Improper installation or use of this product can cause serious bodily injury or
death!
1)
NEVER smoke near the pump, or use the pump near open flames when
pumping a flammable liquid! Fire can result!
2)
A Fill-Rite Filter should be used on the pump outlet to insure no foreign
material is transferred to the fuel tank.
3)
Threaded pipe joints and connections should be sealed with the
appropriate sealant or sealant tape to minimize the possibility of leaks.
4)
Storage tanks should be securely anchored to prevent shifting or tipping
when full or empty.
5)
To minimize static electricity build up, use only static wire conductive hose
when pumping flammable fluids, and keep the fill nozzle in contact with the
container being filled during the filling process.
6)
The pump motor is equipped with thermal overload protection; if
overheated, the motor will shut off to prevent damage to the windings. If
this happens, TURN THE PUMP OFF! When the motor cools, it will restart
without warning if the power is on.
WARNING! This product shall not be used to transfer fluids into any type of
aircraft.
WARNING! This product is not suited for use with fluids intended for human
consumption or fluids containing water.

Installation

The Fill-Rite Series 700V pump is designed to offer several different mounting configurations.
It can be mounted on a skid tank using the tank adapter supplied with the pump (see attached
diagrams), direct mounted to the top of an underground tank, or mounted on a concrete island
using an optional pedestal adapter (available through your Fill-Rite distributor). Regardless of
mounting style, all tanks must be properly vented, and skid tank installations should employ
an anti-siphon device.
The 700V series pump has a built in check valve with a pressure relief valve to reduce unsafe
excess pressure from thermal expansion of the fluid. It also features an integral bypass valve
to help minimize wear when the pump is operating with the nozzle closed.
WARNING! In "Skid Tank" applications, be sure the tank is properly secured so it
cannot shift or move when the tank is empty or full.
3

Publicité

Table des Matières
loading

Table des Matières