INSTALLATION

CLEARANCES:
TO NON-COMBUSTIBLE CONSTRUCTION
EN
A minimum of 4" [10 cm] clearance from the back of the Deluxe Grill to non-combustible
construction is required to allow the hood to be opened fully.
TO COMBUSTIBLE CONSTRUCTION
This appliance should NOT be installed over, under or next to unprotected combustible
construction. A minimum clearance to vertical combustible material, such as adjacent walls, is 12"
[30 cm] on the sides and the rear of the appliance.
The minimum vertical clearance to combustible materials means that ALL combustible materials
must be outside this 12" [30 cm] zone. As an example, if you have a stucco or tiled surface
and wood-frame construction beneath, or wood-frame walls adjacent or behind, the wood is
considered combustible, even though the grill is mounted in its stainless steel cart. If the grill was
parked close to these surfaces when grilling over an extended period of time, enough radiant heat
could reach the wood and potentially get hot enough to burn, in extreme circumstances.
VENTILATION OPENINGS
There are ventilation openings at the left and right sides, as well as the back and underside of the
Deluxe Grill cart. These openings are required to safely dissipate gas vapors if there is a leak inside.
Do not block any of these vent openings inside the cart with vinyl covers, towels, etc. or block the
vent openings outside the cart either.

GAS CONNECTIONS

GAS SUPPLY
The local gas authority or supplier should be consulted at the installation planning stage in order to
establish the availability of an adequate supply of gas (NG or LP). If it is a new installation, have the
gas authorities or supplier check the meter size and piping to assure that the unit is supplied with the
necessary amount of gas supply and pressure to operate the unit(s).
Gas connections should be made by a qualified plumber, or your professional outdoor appliance
installer.
All fixed (non-mobile) appliances must be fitted with an accessible upstream gas shutoff valve as a
means of isolating the appliance for emergency shut off and for servicing.
Make certain new piping and connections have been made in a clean manner and have been purged so
that piping compound, chips, etc. will not clog regulators, valves, orifices, or burners. Use pipe joint
compound / thread sealant approved for natural and LP gases.
NEVER CONNECT THE GRILL TO AN UNREGULATED GAS SUPPLY. Before proceeding, ensure the
appliance is fitted for Natural or Liquid Propane gas. Connecting to an improper gas type will result in
poor performance and increased risk of damage or injury. Gas type and gas consumption (BTU per hour)
for each burner type is shown on the rating label affixed to the underside of the drip tray.
Installation of this cooking appliance must be made in accordance with local codes. In the absence of
local codes, this unit should be installed in accordance with the National Fuel Gas Code No. Z223.1/
NFPA 54 , Natural Gas and Propane Installation code CSA B149-1 , or Propane Storage and Handling
Code B149.2.
NOTE:
NOTE: See rating label for manifold pressure for the type of gas of your appliance.
12