Installation and Operation Manual
6.

Switching examples

Ensure that suitable interference suppression is
provided when connecting the latch drive and exter-
nal output contactors (RC elements or rapid recov-
ery diodes directly via inductors).
6.1.
Connecting a single-phase latch sole-
noid
K44
K45
K40
K41
K42
K43
Mounting rail
Figure 13: Connection diagram latch solenoid
6.2.
Connecting
solenoid
A three-phase latch motor can be simply connected
by changing the standard wiring of the cegard/Lift
LX. The following existing connections should be
(starting from the situation in figure 11) removed:
Contactor 2-4, contactor 3-5, contactor 1-K44, con-
tactor 6-K45. The wiring should be subsequently
supplemented in accordance with the diagram be-
low.
K40
K41
K42
K43
K44
K45
Mounting rail
Figure 14: Connection diagram latch solenoid
© CEDES/October 2008
Latch
solenoid
Connections already
available
a
three-phase
R
S
T
N
Connections already available
6.3.
Connecting two external output con-
tactors to safety circuit
Check 1
Sicherheitskreis
Sicherheitskreis 1
Sicherheitskreis 1
Sicherheitskreis 2
Sicherheitskreis 2
P
Check 2
Sicherheitskreis
N
Figure 15: Connecting two external output contactors to safety
6.4.

Overriding the light curtain

The light curtain is overridden if Override delay
latch
(Überbrückungsverzögerung ) and Option 2 inputs
receive a negative edge. The Override delay
(Überbrückungsverzögerung) and Option 2 inputs
can be connected in parallel with the Latch_In
(Riegel_In) input if required.
+ Überbrückungs-
verzögerung
- Überbrückungs-
verzögerung
+ Option 2
- Option 2
Figure 16: Overriding the light curtain
www.cedes.com
cegard/Lift LX/LY
K5
K28
K29
K30
K31
K6
circuit
K22
K23
K18
K19
P
H
H
N
P
Floor zone signal
N
P
Opener of the
slow-relays
N
15