S+S Regeltechnik KYMASGARD GW1-RS485-FEM Mode D'emploi page 22

Masquer les pouces Voir aussi pour KYMASGARD GW1-RS485-FEM:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Bit 7 .............. Bit 0
SB 1 .............. 0xA5
SB 2 .............. 0x5A
Typ ................ 8B
ORG ............... B4
DB 3 .............. 00
DB 2 .............. 00
DB 1 .............. 00, FF
DB 0 .............. Size (1... 20h)
ID3 ................ ID No. of gateway
ID2 ................ ID No. of gateway
ID1 ................ ID No. of gateway
ID0 ................ ID No. of gateway
Status ............ FF
Chks .............. Check sum
Bit 7 .............. Bit 0
SB 1 .............. 0xA5
SB 2 .............. 0x5A
Typ ................ 8B
ORG ............... B5
DB 3 .............. 00
DB 2 .............. 00
DB 1 .............. 00
DB 0 .............. 00
ID3 ................ ID No. of gateway
ID2 ................ ID No. of gateway
ID1 ................ ID No. of gateway
ID0 ................ ID No. of gateway
Status ............ 00, FF
Chks .............. Check sum
Bit 7 .............. Bit 0
SB 1 .............. 0xA5
SB 2 .............. 0x5A
Typ ................ 8B
ORG ............... D0
DB 3 .............. New ID No.
DB 2 .............. New ID No.
DB 1 .............. New ID No.
DB 0 .............. New ID No.
ID3 ................ Old ID No.
ID2 ................ Old ID No.
ID1 ................ Old ID No.
ID0 ................ Old ID No.
Status ............ 00, 01, 02, F7
Chks .............. Check sum
Bit 7 .............. Bit 0
SB 1 .............. 0xA5
SB 2 .............. 0x5A
Typ ................ 8B
ORG ............... EB
DB 3 .............. 00
DB 2 .............. 00
DB 1 .............. 00
DB 0 .............. 00
ID3 ................ TG-ID3
ID2 ................ TG-ID2
ID1 ................ TG-ID1
ID0 ................ TG-ID0
Status ............ 00
Chks .............. Check sum
Bit 7 .............. Bit 0
SB 1 .............. 0xA5
SB 2 .............. 0x5A
Typ ................ 8B
ORG ............... EB
DB 3 .............. 00
DB 2 .............. 00
DB 1 .............. 00
DB 0 .............. 00
ID3 ................ ID No. of gateway
ID2 ................ ID No. of gateway
ID1 ................ ID No. of gateway
ID0 ................ ID No. of gateway
Status ............ 00
Chks .............. Check sum
1.11
Gateway Replay INFI Size/Mode
(RMT Receive Message Telegram)
The gateway sends this telegram to the master
after the master has sent a query for the number of transmitter IDs learned
in the input filter.
DB0 (BM) → In DB0 the number of transmitters already learned is indicated.
Possible range from 0 to 32 (20h).
As soon as a transmitter ID is learned, the input filter is active.
DB1 = FF → In DB1 the number of transmitters already learned is indicated.
Possible range from 0 to 32 (20h).
If the number of transmitter IDs learned is 0, the input filter is inactive.
All telegrams received from the gateway are sent to the master.
Using the command "Master Set INFI Disable" (TCT Transmit Command Telegram, see 2.6),
the master can explicitly control and override the filter function.
1.12
Gateway INFI Disable
(RMT Receive Message Telegram)
The gateway sends this telegram to the master
after the master has switched the input filter (INFI) active or inactive.
Status = 00 → Input filter active
(addresses being are filtered)
Status = FF → Input filter inactive
(no address filtering taking place)
1.13
Gateway Replay Stat Base ID change
(RMT Receive Message Telegram)
The gateway sends this telegram to the master
after the master has changed the subscriber ID number of the gateway.
Status = 00 → New subscriber ID number was set
Status = 01 → Requested subscriber ID number not within the permissible range
Status = 02 → Change of subscriber ID number no longer possible
Status = F7 → Gateway not in LRN mode
1.14
Gateway Message TRT-Buffer is full
(RMT Receive Message Telegram)
The gateway sends this TRT telegram to the master
when the last telegram sent by the master could not be executed by the gateway.
In bytes ID3 through ID0, the transmitter ID number is indicated that the master wanted
to send.
1.15
Gateway Message TCT-Buffer is full
(RMT Receive Message Telegram)
The gateway sends this TRT telegram to the master
when the last TCT Telegram sent by the master could not be executed by the gateway.
In bytes ID3 through ID0, the subscriber ID number of the gateway is indicated.