Description and meaning of the alarms
CODE ALARM
A01
Undercompensation
A03
Current too low
A04
Current too high
A05
Voltage too low
A06
Voltage too high
A07
Panel temperature too high
A08
Capacitor current overload
A09
No-Voltage release
A11
Harmonic protection Module nr. n Current too high
A12
Harmonic protection Module nr. n THD-I too high
A19
Slave xx link error
A20
Clean the air filter
A21
Routine maintenance
A22
Extraordinary maintenance
4.
CONNECTION OF THE LINE CURRENT TRANSFORMER
Mount the current transformer on the phase non concerned with the pick-up of the voltage signal by the reactive power regulator (usually phase L1
also marked by R) and before the branch supplying the power factor correction board (the transformer should measure the current of the loads plus
that of the power factor correction board).
The current transformer should be of class 0,5 or 1 with apparent power at least 6VA. If other loads are present in parallel to the current transformer,
check their power consumption; increase the apparent power if necessary. When the distance of the current transformer from the unit is less than or
2
equal to 20m use 4mm
cables for connection; if not, increase the size of the cables (for further information, consult the ICAR Technical Service
department).
5.
LIABILITY
ICAR S.p.A. shall not be liable for direct or indirect damage caused to people or objects in case of incorrect mounting of the units or inappropriate use
of such units.
INFORMATION AND TECHNICAL SERVICE
For information, please contact:
Sales Department: sales@icar.com
Technical Service: tech.cv@icar.com
MEANING
All the available steps are connected but the cosφ is still more inductive than the
setpoint.
The current flowing in the current inputs is lower than minimum measuring range.
This condition can occour normally if the plant has no load.
The current flowing in the current inputs is lower than minimum measuring range.
The measured voltage is lower than the threshold set with P17.14.
The measured voltage is higher than the threshold set with P17.13.
The panel temperature is higher than threshold set with P17.06.
The calculated capacitor current overload is higher than threshold set with P17.08
and/or P17.09.
A no-voltage release has occurred on the line voltage inputs, lasting more than 8ms.
The RMS current measured by the MCP5 module n is higher than threshold set with
P18.n.06.
The current THD measured by the MCP5 module n is higher than threshold set with
P18.n.07.
The slave nr. X does not communicate with the master. Check the RS-485 wiring.
Clean the air intake filter of the ventilation system.
Check the currents for each step, the efficiency of the fuses and contactors.
Perform the operations in A20 and A21 and check the capacitors conditions or
contact technical service.