Airwell YEVFD Série Manuel D'installation page 31

Masquer les pouces Voir aussi pour YEVFD Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 63
Failure code
Digital tube
Indication
indication
on wired
on master
controller
unit
(hex)
Voltage too low of DC bus
114
114
line of transducer
Voltage too high of DC
115
115
bus line of transducer
Communication abnormal
116
116
between transducer and
control PCB
Transducer over current
117
117
(software)
Compressor startup
118
118
failure
Detecting circuit of
119
119
transducer current is
abnormal
Power supply of
120
120
transducer abnormal
Power supply of inverter
121
121
board is abnormal
Radiator temp.sensor of
122
122
transducer abnormal
Transient over current in
123
123
IPM module rectifier side
hardware
When there is no failure, if the starting condition can not be met, digital tube on master unit will display stand-by code:
Standby state of capacity
555.0
overmatch
Outdoor ambient temperature
555.1
too high (heating)
Outdoor ambient temperature
555.3
too high or too low (cooling)
Indoor failure code list
Indication on
Indication on wired
master unit
controller
01
01
02
02
03
03
04
04
05
05
06
06
07
07
08
08
09
09
0A
0A
Outdoor
Outdoor failure
failure code
code
Failure code definition
Failure description
Voltage of power source is too low
Voltage of power source is too high
Communication is disconnected
Compressor startup fails for 5 times continuously, or
compressor is running down till stops caused by over
current or over heat
The sensor used for current detecting of transducer
is abnormal, disconnected or incorrectly connection
Current detection sensor of frequency controller is
abnormal or unconnected or connected wrongly.
Power supply of transducer is broken down instantly
Power supply of inverter board is broken down
instantly
Resistor of temp.sensor abnormal or temp.sensor
disconnected
Transient over current in IPM module rectifier side
hardware
When the ratio of indoor horse power and outdoor horse power is
less than 50% or more than 130%, the system is in standby mode.
Ta>27°C, Standby
Ta>54°C or Ta<-15°C, Standby
Flash times of LED5 on
indoor PCB/timer LED
on remote receiver
1
2
3
4
5
6
7
8
9
10
20
Failure code definition
Indoor ambient temp. sensor Ta failure
Indoor coil temp. sensor Tc1 failure
Indoor coil temp. sensor Tc2 failure
Indoor TW sensor failure
Indoor EEPROM failure
Communication between indoor and outdoor failure
Communication between indoor and wired controller failure
Indoor drainage failure
Indoor repeated address
Indoor repeated central control address
Outdoor corresponding failure
23
Remarks
3 times in an
hour, confirm
failure; once
confirmation,
un-resumable
Resumable
3 times in an
hour, confirm
failure; once
confirmation,
un-resumable
3 times in an
hour, confirm
failure; once
confirmation,
un-resumable
Resumable

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Aw-yevfd125-h15Aw-yevfd150-h15Aw-yevfd150-h16

Table des Matières