Installing The Reliseal V 510 - HellermannTyton Reliseal Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 23
Installation

5 .2 Installing the Reliseal V 510

Proceed as follows:
1 Strip the cable as shown in the figure and align the
cores.
15 mm
45 mm
Stripping the cable.
2 Depending on the cable diameter, insert or remove the
adapter seals in the cable joint.
Inserting the adapter seals.
f Select the adapter seals for the corresponding cable
diameter.
Ø14 - 17 mm
Ø18 - 21 mm
Selecting the adapter seals.
8
14 - 21 mm
3 x 4 - 5 x 10 mm²
Installation instructions • Reliseal • 07-2016
3 Connect the cores with the connector block.
f Observe the tightening torque of 3 Nm.
Connecting the cores.
4 Insert the cable connection into the bottom shell.
Inserting the cable connection.
5 Close the cable joint until the fasteners engage.
Closing the cable joint.

Publicité

Table des Matières
loading

Table des Matières