Digital Inputs - Grundfos MAGNA3 65-XX Notice D'installation Et De Fonctionnement

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5.5.2 Digital inputs

See fig. 15, pos. 2.
The digital input can be used for external control of start/stop or
forced max. or min. curve.
If no external on/off switch is connected, the jumper between
terminals Start/Stop (S/S) and frame ( ) should be maintained.
This connection is the factory setting.
M
M
A
I
Start/stop
Fig. 18 Digital input
Contact symbol
M
A
M
I
S/S
External start/stop
The pump can be started or stopped via the digital input.
Start/stop
S/S
H
S/S
H
Q
18
S/S
On/off timer
Function
Max. curve
100 % speed
Min. curve
25 % speed
Start/Stop
Frame connection
Normal duty
Note: Factory setting with
jumper between S/S and
Q
Stop
External forced max. or min. curve
The pump can be forced to operate on the max. or min. curve via
the digital input.
M
H
A
M
H
A
M
H
I
M
H
I
Select the function of the digital input on the pump control panel
or with Grundfos GO Remote.
.
Max. curve
Normal duty
Q
Max. curve
Q
Min. curve
Normal duty
Q
Min. curve
Q