1. Size of BC controller's end connection piping
[Fig. 5.2.2]
BC CONTROLLER/MAIN BC CONTROLLER
Unit model
Model name
(BC CONTROLLER)
PURY-P72
CMB-P104NU-G1
CMB-P105NU-G1
CMB-P106NU-G1
PURY-P96
CMB-P108NU-G1
CMB-P1010NU-G1
CMB-P1013NU-G1
PURY-P120
CMB-P1016NU-G1
PURY-P144
PURY-P168
(MAIN BC
CONTROLLER)
CMB-P108NU-GA1
PURY-P192
CMB-P1010NU-GA1
CMB-P1013NU-GA1
PURY-P216
CMB-P1016NU-GA1
PURY-P240
(MAIN BC
PURY-P264
CONTROLLER)
CMB-P108NU-HA1
CMB-P1010NU-HA1
PURY-P288
CMB-P1016NU-HA1
Indoor unit side
A B
C
G
*2
D
*1
E
E
E
F
24-54
72-96
A To outdoor unit (MAIN BC CONTROLLER)
B End connection (brazing)
C BC controller (MAIN BC CONTROLLER / SUB BC CONTROLLER)
D Reducer (accessory)
F Less than 18
G Combined piping kit (Model name: CMY-R160-J1)
H Twinning pipe (Model name: CMY-Y102S-G2)
I Up to three units for 1 branch hole; total capacity: below 30 (but same in cooling/heat-
ing mode)
The size of BC controller's branch piping is for 63 to 140 type indoor units.
Therefore, if you want to connect indoor units other than the above, connect pip-
ing following the procedures below.
*1. For connecting 06 to 18 type indoor units
Connect indoor units using the reducers supplied with BC controllers.
Note:
*2. To connect a unit with a capacity of higher than 31.
After combining two branches using an optionally available piping kit
(CMY-R160-J1), connect indoor units.
*3. Connection of plural indoor units with one connection (or joint pipe)
joint pipe)
G2)
Select the size according to the total capacity of indoor units to be installed
downstream.
Total capacity of indoor units
Below 54
55 to 72
73 to 96
10
High pressure
Low pressure
Model name
side (mm [in])
side (mm [in])
ø15.88 [5/8]
ø19.05 [3/4]
(Brazing)
(Brazing)
ø22.2 [7/8]
(Brazing)
ø19.05 [3/4]
When a system that has more than 16 branching points, use BC controllersì
(Brazing)
(main and sub) to connect the pipes.
ø25.4 [1]
(Brazing)
ø22.2 [7/8]
(Brazing)
ø28.58 [1-1/8]
(Brazing)
CMB-P104NU-GB1
CMB-P108NU-GB1
CMB-P1016NU-HB1
ø28.58 [1-1/8]
(Brazing)
ø34.93 [1-3/8]
(Brazing)
ø9.52 [3/8]
ø15.88 [5/8]
(Flare)
(Flare)
H
E
E
E
I
*3
E Indoor unit
(Unit: mm [in])
Liquid line
Gas line
ø15.88 [5/8]
ø9.52 [3/8]
ø19.05 [3/4]
ø22.2 [7/8]
SUB BC CONTROLLER
Total capacity of
High pressure
indoor units
(gas) side (mm [in])
ø15.88 [5/8]
below 72
(Brazing)
73-108
ø19.05 [3/4]
(Brazing)
109-126
127-144
ø22.2 [7/8]
(Brazing)
145-168
ø9.52 [3/8]
(Flare)
2. Connecting to out side pipes
[Fig. 5.2.3]
High pressure/low pressure piping diagram
B
C
A Connection pipe of outdoor unit (Low pressure)
B Connection pipe of outdoor unit (High pressure)
C Drain piping (O.D.
ø
32mm [1-1/4 in])
D Connection pipe of indoor unit (Liquid)
E Connection pipe of indoor unit (Gas)
Note:
Be sure to use non-oxidative brazing.

5.3. Refrigerant piping work

After connecting the refrigerant pipes of all indoor and outdoor units with the out-
door units' stop valves remained fully closed, evacuate vacuum from the outdoor
units' stop valve service ports.
After completing the above, open the outdoor units' stop valves. This connects
the refrigerant circuit (between outdoor and BC controller) completely.
How to handle stop valves is described on each outdoor unit.
Notes:
Use two wrenches for pipe connection.
After pipe connection, be sure to check that there is no gas leakage,
using a leak detector or soap-and-water solution.
Before brazing the refrigerant piping, always wrap the piping on the main
body, and the thermal insulation piping, with damp cloths to prevent
heat shrinkage and burning the thermal insulation tubing. Take care to
Do not use leak-detection additives.
Warning:
refrigerating cycle when installing or moving. Mixing air may cause the
refrigerating cycle to reach abnormally high temperature, resulting in burst
pipes.
Low pressure (gas)
Liquid side
side (mm [in])
(mm [in])
ø19.05 [3/4]
(Brazing)
ø9.52 [3/8]
(Brazing)
ø22.2 [7/8]
(Brazing)
ø12.7 [1/2]
(Brazing)
ø28.58 [1-1/8]
(Brazing)
ø15.88 [5/8]
(Brazing)
ø15.88 [5/8]
(Flare)
*1 Use the supplied pipe.
(Unit: mm [in])
D
A