Fixing Hanging Bolts; Installing The Unit; Refrigerant Piping Work - Mitsubishi Electric Mr.Slim PEA-M200LA Manuel D'installation

Masquer les pouces Voir aussi pour Mr.Slim PEA-M200LA:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 34

4. Fixing hanging bolts

4.1. Fixing hanging bolts
[Fig. 4-1]
W
X
A Center of gravity
(Give site of suspension strong structure.)
Center of gravity and Product Weight
Model name
PEA-M200,250LA

5. Installing the unit

5.1. Hanging the unit body
 Bring the indoor unit to an installation site as it is packed.
 To hang the indoor unit, use a lifting machine to lift and pass through the
hanging bolts.
[Fig. 5-1-1]
A
B
A Unit body
B Lifting machine

6. Refrigerant piping work

6.1. Refrigerant pipe
[Fig. 6-1]
øB
a
øA
a Indoor unit
b Outdoor unit
Model
A
M200
ø25.4
ø9.52
M250
ø25.4
ø12.7
Refer to the Instruction Manual that came with the outdoor unit for the restrictions on
the height difference between units and for the amount of additional refrigerant
charge.
Avoid the following places for installation where air conditioner trouble is liable to
occur.
• Where there is too much oil such as for machine or cooking.
• Salty environment as seaside areas.
• Hot-spring areas.
• Where sulfide gas exists.
• Other special atmospheric areas.
L
Y
A
W (mm)
L (mm)
1034
1326
b
B
Hanging structure
• Ceiling: The ceiling structure varies from building to one another. For detailed
information, consult your construction company.
• If necessary, reinforce the hanging bolts with anti-quake supporting members as
countermeasures against earthquakes.
* Use M10 for hanging bolts and anti-quake supporting members (field supply).
a Reinforcing the ceiling with additional members (edge beam, etc.) must be
required to keep the ceiling at level and to prevent the ceiling from vibrations.
b Cut and remove the ceiling members.
c Reinforce the ceiling members, and add other members for fixing the ceiling
boards.
X (mm)
Y (mm)
Z (mm)
462
660
[Fig. 5-1-2]
C
D
D
C
E
C Nuts (field supply)
D Washer (accessory)
E M10 hanging bolt (field supply)
5.2. Confirming the unit's position and fixing hanging
bolts
 Ensure that the hanging bolt nuts are tightened to fix the hanging bolts.
 To ensure that drain is discharged, be sure to hang the unit at level using a
level.
Caution:
Install the unit in horizontal position. If the side with drain port is installed
higher, water leakage may be caused.
• This unit has brazed connections on both indoor and outdoor sides. [Fig. 6-1]
• Insulate both refrigerant and drainage piping completely to prevent condensation.
Piping preparation
• Refrigerant pipes of 3, 5, 7, 10 and 15 m are available as optional items.
(1) Table below shows the specifications of pipes commercially available.
Outside diameter
Model
Pipe
mm
inch
For liquid
9.52
PEA-
M200
For gas
25.4
For liquid
12.7
PEA-
M250
For gas
25.4
(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
(3) Refrigerant pipe bending radius must be 10 cm or more.
Caution:
Using careful insulation of specified thickness. Excessive thickness prevents
storage behind the indoor unit and smaller thickness causes dew drippage.
Warning:
To reduce the risk of fire, embed or protect the refrigerant pipes. Damage to
the refrigerant pipes can lead to fire.
Product Weight (kg)
235
87
Min. wall
Insulation
Insulation
thickness
thickness
material
3/8
0.8 mm
8 mm
Heat resisting
1/1
1.0 mm
8 mm
foam plastic
0.045 specific
1/2
0.8 mm
8 mm
gravity
1/1
1.0 mm
8 mm
5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mr.slim pea-m250la

Table des Matières