Refrigerant Piping Work; Refrigerant Pipe; Pipe Connection; Flaring Work - Mitsubishi Electric Mr.SLIM PEAD-A24AA Manuel D'installation

Masquer les pouces Voir aussi pour Mr.SLIM PEAD-A24AA:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6. Refrigerant piping work

6.1. Refrigerant pipe

[Fig. 6-1] (P.3)
a Indoor unit
b Outdoor unit
Refer to the Instruction Manual that came with the outdoor unit for the restrictions on
the height difference between units and for the amount of additional refrigerant
charge.
Avoid the following places for installation where air conditioner trouble is liable to
occur.
• Where there is too much oil such as for machine or cooking.
• Salty environment as seaside areas.
• Hot-spring areas.
• Where sulfide gas exists.
• Other special atmospheric areas.
• This unit has flared connections on both indoor and outdoor sides. [Fig. 6-1]
• Refrigerant pipes are used to connect the indoor and outdoor units as shown in the
figure below.
• Insulate both refrigerant and drainage piping completely to prevent condensation.
Piping preparation
• Refrigerant pipes of 3, 5, 7, 10 and 15 m [9-13/16, 16-3/8, 22-15/16, 32-1/4 and 49-
3/16 ft] are available as optional items.
(1) Table below shows the specifications of pipes commercially available.
Outside diameter
Min wall thickness
Model
Pipe
mm
inch
mm
PEAD-
For liquid
9.52
3/8
0.8
A24AA
For gas
15.88
5/8
1.0
PEAD-
For liquid
9.52
3/8
0.8
A30AA
For gas
15.88
5/8
1.0
PEAD-
For liquid
9.52
3/8
0.8
A36AA
For gas
15.88
5/8
1.0
PEAD-
For liquid
9.52
3/8
0.8
A42AA
For gas
15.88
5/8
1.0
(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
(3) Refrigerant pipe bending radius must be 10 cm [3-15/16 in] or more.
Caution:
Using careful insulation of specified thickness. Excessive thickness prevents
storage behind the indoor unit and smaller thickness causes dew drippage.

6.2. Flaring work

• Main cause of gas leakage is defect in flaring work.
Carry out correct flaring work in the following procedure.
6.2.1. Pipe cutting
[Fig. 6-3] (P.3)
a Copper tubes
b Good
c No good
d Tilted
e Uneven
f Burred
• Using a pipe cutter cut the copper tube correctly.
6.2.2. Burrs removal
[Fig. 6-4] (P.3)
a Burr
b Copper tube/pipe
c Spare reamer
d Pipe cutter
• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in
order to avoid burrs drop in the tubing.
All manuals and user guides at all-guides.com
6.2.3. Putting nut on
• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube
6.2.4. Flaring work
• Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a die in the dimension shown in the table at above.
Insulation thickness
Insulation
6.2.5. Check
inch
mm
inch
material
1/32
8
5/16
1/32
8
5/16
Heat resisting
1/32
8
5/16
foam plastic
1/32
8
5/16
0.045 specific
1/32
8
5/16
gravity
1/32
8
5/16
1/32
8
5/16
• Compare the flared work with a figure in right side hand.
1/32
8
5/16
• If flare is noted to be defective, cut off the flared section and do flaring work again.

6.3. Pipe connection

• Apply a thin coat of refrigeration oil on the seat surface of pipe.
• For connection first align the center, then tighten the first 3 to 4 turns of flare nut.
• Use tightening torque table below as a guideline for indoor unit side union joint section,
Be careful of flying flare nut! (Internally pressurized)
Remove the flare nut as follows:
1. Loosen the nut until you hear a hissing noise.
2. Do not remove the nut until the gas has been completely released (i.e., hiss-
3. Check that the gas has been completely released, and then remove the nut.
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied
for indoor unit.
• For tightening use a torque wrench or spanner, and use the same tightening torque
[Fig. 6-5] (P.3)
a Flare nut
b Copper tube
having completed burr removal.
(not possible to put them on after flaring work)
[Fig. 6-6] (P.3)
a Flaring tool
b Die
c Copper tube
d Flare nut
e Yoke
Pipe diameter
A (mm [in])
(mm [in])
When the tool for R410A is used
Clutch type
6.35 [1/4]
0 to 0.5 [0 to 1/32]
9.52 [3/8]
0 to 0.5 [0 to 1/32]
12.7 [1/2]
0 to 0.5 [0 to 1/32]
15.88 [5/8]
0 to 0.5 [0 to 1/32]
[Fig. 6-7] (P.3)
a Smooth all around
f Scratch on flared plane
b Inside is shining without any scratches
g Cracked
c Even length all around
h Uneven
d Too much
i Bad examples
e Tilted
[Fig. 6-8] (P.3)
and tighten using two wrenches. Excessive tightening damages the flare section.
Copper pipe O.D.
Flare nut O.D.
(mm [in])
(mm [in])
ø6.35 [1/4]
17 [11/16]
ø9.52 [3/8]
22 [7/8]
ø12.7 [1/2]
26 [1-1/32]
ø15.88 [5/8]
29 [1-5/32]
Warning:
ing noise stops).
applied for indoor unit.
Dimension
+0
B
(mm [in])
-0.4 [-1/32]
9.1 [3/8]
13.2 [17/32]
16.6 [21/32]
19.7 [25/32]
Tightening torque
(N·m)
14 - 18
34 - 42
49 - 61
68 - 82
15

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Mr.slim pead-a30aaMr.slim pead-a36aaMr.slim pead-a42aa

Table des Matières