Plan The Installation; Tools Required - Zephyr Monsoon I Guide D'utilisation, D'entretien Et D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

PLAN THE INSTALLATION

Planning the installation first requires selecting the most appropriate
installation approach. The chart below offers suggestions for the most
effective installation approach by considering a few important factors.
Further details on the two main types of installations are provided below.
• House has central duct work?
Yes
• Return-air side of duct work is
accessible -either the return-air trunk
or return - air plenum?
Yes
Damper connected to
return side of central
duct system
OUTSIDE AIR INTAKE LOCATION
Proper design and location of the outside air intake location is critical in
ensuring that the Damper can safely and reliably provide an opening for
fresh air to enter the home. The following requirements for the location
of the outside air intake must be met:
• Outside air intake is located a minimum of 10' from combustion ap-
pliance vents, chimneys, plumbing stacks, and bathroom or kitchen
exhaust vents. If local codes have more stringent separation re-
quirements, they shall apply.
• Outside air intake is placed high enough above grade to prevent
blockage from snow or other debris such as leaves, and at a mini-
mum of 1' above grade.
• Make-up air damper should not draw air from crawlspaces, ga-
rages, attics, adjacent dwelling units, or any enclosed part of the
building. The Damper should be installed to draw air directly from
outdoors.
OUTSIDE AIR INTAKE OPENING PROTECTION
Because the Damper, together with the end cap and outside air duct
which are installed with it, will allow outdoor air into the indoor environ-
ment, it is important to meet the following requirements:
• Model AK00030 (6"), AK00032 (8") and AK00052 (10") fresh air inlet
wall caps include protective bird screens to keep out animals and
outside debris. Clean screens often and do not remove.
• If a protective bird screen other than the screen provided is used, it
must cover the entire opening of the outside air duct. This screen
must also have openings of at least ¼" but no larger than ½" .
• The outdoor air intake opening should meet local code provisions
for the protection of openings in exterior walls, including steps to
prevent moisture intrusion around the opening.
Note that the screen over the outside air opening is not a filter. It is
intended to prevent the intake of leaves, animals, or debris into the out-
side air duct. A downstream filter is necessary to remove pollen, dust,
and other airborne particles. Potential filter locations are shown below
in the Typical Installations section.
No
No
Damper ducted directly
to a ceiling, floor, or wall
register
MODELS MUA006A • MUA008A • MUA010A
MINIMUM RETURN AIR TEMPERATURE REQUIREMENTS
HVAC equipment manufacturers may have minimum requirements for
the air temperature in the return air plenum. Introducing outdoor air to
the return side of the central duct system may impact this temperature.
The installer should adjust both the size of the outside air duct and the
location of its connection to the return side of the central duct system in
a manner so that minimum air temperature requirements are satisfied
under design conditions.
WHAT IS INCLUDED IN THE
PACKAGE
- Motorized Damper
- Transformer
- Pressure Switch Kit which includes:
- Pressure Switch
- Probe
- 12" PVC tubing 1/4" I.D.
- Gasket
- (6) Sheet Metal Screws

TOOLS REQUIRED

- 1/4" Socket Drive
- Flathead or Phillips Screw Driver
- 3/8" Drill Bit
- Duct Tape
- Low Voltage Wire (2 Conductor)
- (2) 1/4" Female Spade Terminals
- Wire Nuts
Page 3

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ak9228asAk9234asAk9240asAk9246as

Table des Matières