Victron energy MultiPlus 12/3000/120 Manuel page 27

Masquer les pouces Voir aussi pour MultiPlus 12/3000/120:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 57
One alarm LED
The inverter is switched off due to
lights and the
alarm activation by the lighted LED.
second flashes.
The flashing LED indicates that the
inverter was about to switch off due
to the related alarm.
The charger does
The AC input voltage or frequency is
not operate.
not within the range set.
Circuit breaker or fuse in the
AC-in input is open as a result of
overload.
The battery fuse has blown.
The distortion or the AC input voltage is
too large (generally generator supply).
The charger does
MultiPlus is in "Bulk protection" mode
not operate.
thus, the maximum bulk charging time
of 10 hours is exceeded.
"Bulk" LED flashes
and
Such
a
long charging time could
"Mains on" LED
indicate a system error (e.g. a battery
illuminates.
cell short-circuit).
The battery is not
Charging current excessively high,
completely charged.
causing premature absorption phase.
Poor battery connection.
The absorption voltage has been set to
an incorrect level (too low).
The float voltage has been set to an
incorrect level (too low).
The available charging time is too short
to fully charge the battery.
The absorption time is too short. For
adaptive charging this can be caused
by an extremely high charging current
with respect to battery capacity, so that
bulk time is insufficient.
The battery is
The absorption voltage is set to an
overcharged.
incorrect level (too high).
The float voltage is set to an incorrect
level (too high).
Poor battery condition.
The battery temperature is too high
(due to poor ventilation, excessively
high environmental temperature, or
excessively high charging current).
The charging
The battery is over-heated (>50°C)
current drops to 0
as soon as the
absorption phase
initiates.
Defective battery temperature sensor
Check this table for appropriate
measures in regard to this alarm
state.
Ensure that the AC input is between
185 VAC and 265 VAC, and that the
frequency is within the range set
(default setting 45-65Hz).
Remove overload or short circuit on
AC-out-1 or AC-out-2, and reset
fuse/breaker.
Replace the battery fuse.
Turn the settings WeakAC and
dynamic current limiter on.
Check your batteries.
NOTE:
You can reset the error mode by
switching off and back on the
MultiPlus.
The standard MultiPlus factory setting
of the "Bulk protection" mode is
switched on. The "Bulk protection"
mode can be switched off with help of
VEConfigure only.
Set the charging current to a level
between 0.1 and 0.2 times the battery
capacity.
Check the battery connections.
Set the absorption voltage to the
correct level.
Set the float voltage to the correct
level.
Select a longer charging time or
higher charging current.
Reduce the charging current or select
the 'fixed' charging characteristics.
Set the absorption voltage to the
correct level.
Set the float voltage to the correct
level.
Replace the battery.
Improve ventilation, install batteries
in a cooler environment, reduce the
charging current, and connect the
temperature sensor.
Install the battery in a cooler
environment
Reduce the charging current
Check whether one of the
battery cells has an internal
short circuit
Disconnect the temperature sensor
plug in the MultiPlus. If charging
functions correctly after
approximately 1 minute, the
temperature sensor should be
replaced.
23

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Multiplus 24/3000/70Multiplus 48/3000/35

Table des Matières