Gree GMV-H224WL/A-X Manuel D'utilisateur page 31

Table des Matières

Publicité

db
db
15_
Cooling
debugging
db
db
16_
Heating
debugging
db
17_
Debugging
00
finished
5.2.3 Appendix: Reference of normal operation parameters
No.
Debug item
1
2
3
System
parameters
4
5
6
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
On
12
On
On
15
On
On
15
On
On
16
On
On
16
On
AC/A
On
On
H
Parameter name
Outdoor
temperature
Compressor
discharge
temperature
Defrosting
temperature
ODU
parameters
System high
pressure
System low
pressure
Opening angle of
thermal EXV
DC Inverter Multi VRF System
Startup is confirmed. After displaying for
2s, system will choose "15_Cooling
debugging" or "16_Heating debugging"
according to ambient temperature. If the
AE
On
project requests to add refrigerant but
it is not complemented before
debugging, then refrigerant can be
added in this process through the
L-VALVE.
Debugging for cooling mode. If no
malfunction occurs for 20min when
AC
On
compressor is running, then system will
start progress 17; If malfunction
occurs,unit will display as below:
Malfunction occurs when debugging for
cooling mode. After all malfunctions
Error
On
code
are eliminated, system will start next
step.
Debugging for heating mode. If no
malfunction occurs for 20min when
AH
On
compressor is running, then system will
start progress 17; If malfunction
occurs,unit will display as below:
Malfunction occurs when debugging for
Error
heating mode. After all malfunctions
On
are eliminated, system will start next
code
step.
The entire unit has finished debugging
OFF
On
and under standby-by condition.
Unit
●When compressor starts, discharge temp in cool
mode is within 70~105℃ and at least 10℃ higher
than the high pressure saturation temp;
●As for temp in heat mode, it is within 65~90℃
and at least 10℃ higher than the high pressure
saturation temp.
●In cool mode, defrosting temp is 4~10℃ lower
than system's high pressure value;
●In heat mode, defrosting temp is about 2℃
different from system's low pressure value.
●In cool mode, the normal high pressure value is
within 20℃~55℃. According to the change of
ambient temp and system's operating capacity,
the high pressure value will be 10℃~30℃ higher
than ambient temp. The higher ambient temp is,
the smaller temp difference is. If ambient temp is
25~35℃ in cool mode, system's high pressure
value will be within 44~53℃.
●In heat mode, if ambient temp is above -5℃,
system's high pressure value is within 40~52℃. If
ambient temp is low and many IDUs are turned
on, the high pressure will be lower.
●When ambient temp in cool mode is 25~35℃,
the low pressure value is 0~8℃.
●When ambient temp in heat mode is above -5℃,
the low pressure value is -15~8℃.
●In cool mode, the thermal electronic expansion
valve remains 480PLS.
PLS
●In heat mode, the adjustable opening angle of
EXV is 60~480PLS.
28
Reference
——

Publicité

Chapitres

Table des Matières
loading

Table des Matières