DC Inverter Multi VRF System
Fig.5 Allowable Length and Height Difference of Connection Pipe
Piping parameters of
GMV-H224WL/A-X,GMV-H280WL/A-X,GMV-H335WL/A-X,GMV-224WL/C-X,GMV-280WL/C-X,G
MV-335WL/C-X:
Total length (actual length) of fitting pipe
Length of farthest fitting pipe (m)
From the 1
Height difference between ODU
and IDU
Height difference between IDUs
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Actual length
Equivalent length
st
branch to the farthest indoor pipe
ODU at upper side
ODU at lower side
Allowable
value
300m
120m
150m
40m
50m
40m
15m
9
Fitting pipe
L1+L2+L3+a+b++c+d
L1+L2+L3+d
L2+L3+d
——
——
——