Hazardous (Classified) Location
Class I, Division 1, Groups A, B, C, D
Class II, Division 1, Groups E, F, G
Class III
T4 @ T a = – 40°C to + 80°C
SITRANS
Probe LU
(PROFIBUS PA)
Notes:
1. The non-intrinsically safe terminals (power rail) must not be connected to any device which uses or generates more
than 250 Vrms or dc unless it has been determined that the voltage has been adequately isolated.
2. In the USA the installation must meet the requirements of the National Electrical Code, NFPA 70. article 504 resp.
article 505 and ANSI / ISA RP 12.6 . In Canada observe the Canadian Electrical Code.
3. Multiple earthing of screen is allowed only, if high integrity equipotential system is realized between the points of bonding.
FOR INTERNAL
USE ONLY
Page A-4 SITRANS Probe LU (PROFIBUS PA) – QUICK START MANUAL
Entity parameters:
Terminals
and
U , V
= 24 V
i
max
I , I
= 250 mA
i
max
P , P
= 1.2 W
i
max
C
= 0.5 nF
i
L
= 0
i
0
Product Group
ULTRASONICS
18 / APRIL / 2005
R. CLYSDALE
E. DeSIMONE
S. NGUYEN
PETERBOROUGH
2365061700
Non-Hazardous Location
Intrinsic safety barrier
V
V
For Intrinsic safety application use CSA / FM
approved associated apparatus or barrier
Entity parameters:
£
V
or V
24 V
oc
t
£
I
or I
250 mA
s
c
t
£
P or P
1.2 W
o
t
³
C
0.5 nF + C
a
cable
³
L
0 + L
a
cable
FOR CONSTRUCTION
SITRANS Probe LU
PROFIBUS PA
CONNECTION DRAWING
23650617
1 : 1
See Note 1
APRIL
RPC
SN
18 / 2005
A
NTS
0
4
4
7ML19985QV81