1. Remove station housing from backplate/button assembly by removing the attachment screw
on the bottom of the housing using the 3/32" hex key provided.
2. A ground lug is provided for the attachment of any ground wires to the backplate/button
assembly.
3. Carefully fit the connection wires and terminal assembly inside the electrical box.
4. Attach backplate/button assembly to the electrical box using the #6-32 x 7/8" screws
provided.
5. Replace station housing on backplate/button assembly and re-attach the bottom screw
removed earlier. Use the 3/32" hex key.
D. Installation of Sounder-Cover (PSEMSC-R and PSEVSC-Y models only).
1. Hold mounting frame over unit to be protected and mark four holes for installation.
2. Drill four 1/4" holes approximately 1-1/4" deep.
3. Place anchors (provided) into mounting holes.
4. Place entire cover assembly over unit to be protected.
5. Remove deactivation pin from back of Sounder-Cover. Horn should sound.
6. Close cover.
The sounder utilized in the Sounder-Cover is powered by a replaceable 9VDC battery
(included.)
III. TEST AFTER INSTALLATION.
Check for proper operation of all push button stations installed in your system. Depress the
activation button inward until button locks into place and completes the circuit to the alarm panel.
Resetting of the station is accomplished by grasping the activation button and rotating approxi-
mately 45 degrees clockwise. The activation button should return to its initial position. Do not
over rotate the activation button as this may cause permanent damage to the unit.
IV. MAINTENANCE/SERVICE.
The Federal factory will service your equipment or provide technical assistance with any
problems that cannot be handled locally.
Any units returned to Federal Signal for service, inspection, or repair must be accompanied by a
Return Material Authorization (R.M.A.) This R.M.A. may be obtained from a local distributor or
manufacturer's representative.
At this time a brief explanation of the service requested, or nature of the malfunction, should be
provided.
Address all communications and shipments to:
FEDERAL SIGNAL CORPORATION
Electrical Products Division
Service Department
2645 Federal Signal Drive
University Park, IL 60466-3195
(708) 534-3400