Using the GFX3 Humidistat

Press
to select OFF, MANUAL or AUTO mode (if outdoor sensor is connected).
OFF mode: The humidifier is turned off.
MANUAL mode: The GFX3 will work to maintain the single humidity selected. You can set
your desired humidity level by pressing
according to your manual setting. (The humidifier will operate when the measured relative
humidity falls more than 2% below the set point.) Humidity will have to be lowered when
weather is colder or if condensation is suspected.
AUTO mode: The GFX3 will automatically raise the humidity as the outdoor temperature
increases. This provides the highest possible humidity. The GFX3 will automatically lower the humidity as temperatures drop. This
minimizes the risk of condensation on cold surfaces like windows. You can adjust the Auto Humidity Index Set Point from 0 (low) to
10 (high) by pressing
or
switch ON/OFF according to the calculated auto humidity index set point. Lower Index settings are for older homes with less
insulation and vapor barriers. Higher Index settings are for newer homes with complete vapor barriers, triple pane windows and high
R value insulation. If condensation occurs reduce Index setting by 2 points until condensation stops.
NOTE If the outdoor temperature sensor fails,
To toggle between indoor / outdoor temperature and indoor humidity: Press
To change the temperature unit: Press °C / °F.
To set the temperature / humidity offset in MANUAL or AUTO mode:
1.
Simultaneously press
2.
Use
or
to change the setting (-3 to 3).
3.
Press
and
simultaneously or wait 5 seconds to confirm and move onto the next setting.
WARNING: Do not allow excess humidification. Excess humidity can cause condensation and enable mold and mildew growth.
5.6

Alarms

In the event of an alarm, the red alarm LED will flash, the alarm relay will close, and the alarm code will flash in the display. Multiple
alarms will flash in sequence, alternating with the main display. Pressing the sel button for 2 seconds will reset the alarms, although
still active alarms will continue to display.
Dis
Description
play
--
Remote on-off open
EE
Internal memory error
E0
Control board configuration not valid
E1
High current alarm
E2
Low production, low supply water
conductivity or excessive
foam/limescale in the cylinder
E3
Cylinder almost exhausted, already
used for 2000 hrs
E4
Fill alarm, unable or slow fill
(current does not increase within
timeout)
E5
Drain alarm, unable to drain
(current does not decrease within
timeout)
E6
Cylinder exhausted
(critical performance detected)
E7
Foam detected
E8
Cylinder lifetime expired (3000 hours)
E9
High controller temperature (above
176 °F / 80 °C)
Elite Steam +030222075 Rev. 4.0 – 2 Mar. 2015
or
. The humidifier will turn ON or OFF
. The Humidity Index is based on the outdoor temperature and indoor humidity. The humidifier will
flashes and the unit will default to MANUAL mode.
and
when viewing the temperature or humidity reading.
Unit disabled
Unit disabled
Unit disabled
Unit disabled
Unit disabled.
Press "reset/sel" key for 1 seconds to reset.
Press "reset/sel" key for 1 seconds to reset.
Press "reset/sel" key for 1 seconds to reset, otherwise
the warning will be reset automatically every 10
minutes until the supply water is available again.
Press "reset/sel" key for 1 seconds to reset
The warning is automatically reset if Elite Steam can
produce the demand, otherwise turn off and then on.
Press "reset/sel" key for 1 seconds to reset
Unit disabled: Reset the hour counter (read chap.
Resetting the hour counter")
The warning is automatically reset if the temperature
decreases below 176 °F / 80 °C.
.
Action
Red
Off
On
On
On
On
Off
On
On
Off
Off
On
Off
18
Suggested
Setting
15%
20%
25%
30%
35%
40%
Alarm
Led
Relay
Off
On
On
Turn off, check control board, reprogram
On
Turn off, check connections, check
cylinder (no limescale bridges between
electrodes, no electrodes short-circuited)
On
Check supply water conductivity (too
low?), replace the cylinder.
Off
Change cylinder (not urgent)
On
Check water supply and fill valve; check
drain pump for leakage
On
Check drain pump and drain connection
Off
Change cylinder (urgent)
Off
If it continues, do some cleaning cycles
(read chap. "Starting with a new
cylinder")
On
Change the cylinder if necessary
Off
Check the ambient temperature, replace
the controller.
Outdoor
Temperatures
-20˚F
-29˚C
-10˚F
-23˚C
0˚F
-18˚C
+10˚F -12˚C
+20˚F
- 7˚C
+30˚F
- 1˚C
Notes