3.3.3 Water Drain

The Elite Steam also requires a connection to a drain. The drain line may be routed out the
back or bottom of the unit using the included angle fitting. The drain line can be 1-1/4" PVC,
CPVC or polypropylene. The drain line is not glued or otherwise attached to the humidifier so
it must be supported by itself. A coupling should be used. The Elite Steam includes a drain
tempering valve that runs whenever the drain pump runs and flushes cool water into the drain
line to insure the drain water temperature never exceeds 60°C or 140°F.
The drain water characteristics are:
Drain Flow Rate – See Technical Specifications (Section 8 / pg 24)
Connection 32mm or 1 1/4"
Temperature 60°C or 140°F
IMPORTANT: Drain line must be trapped under the unit to prevent flash steam from
condensing in the unit cabinet, as seen in figure 3.h.2.

3.3.4 Drain Connections

When using a rear outlet drain passing through drywall, we suggest using a 1 1/4" extension tube type SJ (see Fig. 3.f).
When using a bottom outlet drain, attach the included 90° fitting to the drain outlet. The drain outlet may be rotated. Then
connect a 1 1/4" trap adaptor to connect to drain pipe.
WARNING: The drain pipe must be free without back pressure. We recommend an external anti-flooding device not supplied
to protect from faults of external hydraulic circuits.
3.3.5 Condensate Pump
When using a Condensate Pump, ensure pump selected is capable of handling 7.0 GPM for up to 10-15 seconds.

3.4 Steam distribution

3.4.1
Duct steam injection (Additional kit required)
The maximum allowed duct static pressure is 2 in WC.
The Elite Steam duct injection models include a plastic duct injection nozzle. See Fig. 3.i
Millimeters
Inch
A
31.5 mm
1.24"
B
50 mm
1.96"
C
56 mm
2.20"
D
57.5 mm
2.26"
E
100 mm
3.93"
∅ 8 mm
∅ 0.31"
F
∅ 22 mm
∅ 0.86"
G
∅ 30 mm
∅ 1.18"
H
I
12 or 22 mm
0.47 or 0.87"
Airflow
1000 cfm min.
8" min
24" min
Upstream
Important: Do NOT install into duct that has interior insulation.
Elite Steam +030222075 Rev. 4.0 – 2 Mar. 2015
Fig. 3.i
=
=
36"min
Downstream
Height >8"
Airflow
1000 cfm min.
1/3 Height
Fig. 3.j
10
Important: Do NOT install into duct that has interior insulation.
Figure 3.h.2.
Min 8"
Airflow
=
Airflow 1000 cfm min.
=
min. 5°
Air Brake
4
5