Room Ventilation And Stoves; Using The Wood Burning Stove; Adjustment Of Air Damper; Control - RAIS Q-Tee Manuel D'utilisateur

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 149
English
RAIS - Manual for RAIS Q-Tee
By setting the interval between position 1 and 2, the energy content in the firewood is
used optimally, as there is oxygen for combustion and for the burning of the pyrolysis
gasses. When the flames are a clear yellow the damper has been set correctly. Finding the
correct position comes with time after you have used for stove for a while.
It is not recommended that you turn it down completely. A mistake commonly made is
shutting the damper too early because it feels too hot. This results in dark smoke ema-
nating from the chimney and in the calorific value of the firewood not being used to its
fullest.

Room ventilation and stoves

There must not be an extractor fan fitted in the same room as the stove as this can cause
the stove to emit smoke and fumes into the room.
The stove requires a permanent and adequate air supply in order for it to operate safely
and efficiently.
In accordance with current Building Regulations the installer may have fitted a permanent
air supply vent into the room in which the stove is installed to provide combustion air. This
air vent should not under any circumstances be shut off or sealed.

Using the wood burning stove

Adjustment of the air damper - the damper has 3 settings
(see front of manual)
Position 1
The damper is almost closed meaning that there is a minimal air intake.
Position 2
Pull the lever until first click. This position gives full secondary air.
During normal stoking the lever is set between position 1 and 2. When the flames are
clear and yellow, the damper is set correctly, i.e. resulting in a slow / optimal burning.
Position 3
Pull the lever until next click.
The air damper is completely open and gives full primary and secondary air. The position is
for the lighting stage and is not used under normal operation.

Control

If the ash is white and the walls in the combustion chamber soot-free after the stove has
been used, the air regulation was set correctly and the wood was sufficiently dry.
55

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Q-tee wallQ-tee insert

Table des Matières