The drinking water of the DHW tanks of NETZERO CW must be filled with potable water, with a chloride concentration below 250mg
/ l.
R
isk of damage due to inadequate water.
DANGER!
D
eposits caused by unsuitable water can damage the source, the pipes, the heating exchangers and
the DHW tank of the heat pump.
T
he use of seawater is not allowed.
T
he quality of drinking water must comply with the applicable regional regulations and the
instructions contained in this manual.
Electrical system
Any intervention on the electrical system must only be performed by an authorised electrician in accordance with applicable local
regulations and the instructions provided in this manual.
R
emember that the heat pump has multiple external power supply.
DANGER!
T
he heat pump must be supplied with an external switch that can shut off all the circuits. GEOSMART
ENERGY recommend installing one external automatic breaker in each external power supply (control,
internal auxiliary equipment and drive).
B
efore performing any operation on the electrical panel, disconnect the power supply.
D
uring installation and maintenance of the equipment never leave the electrical panel unattended
while it is exposed.
D
o not touch any component of the electrical panel with wet hands as this could cause an electric
shock.

1.2. Recycling

The heat pump uses R410A refrigerant in its circuit. This refrigerant is not harmful to the environment, but once its useful life cycle
has finished, the refrigerant must be recovered and recycled or disposed of according to current regulations.
The heat pump cannot be disposed of with household waste when its useful life ends. Carry out the elimination of the appliance in
accordance with the pertinent local regulations, in a correct and respectful way with the environment. Put the product at the end of
its useful life in the hands of the waste manager authorized by the local authorities for transport to an appropriate treatment plant.
GEOSMART ENERGY
Water properties
pH
Hardness
Electric conductivity
Table 1.2. Water properties limits for production and source circuit.
Limit values
7.5<pH<9
4<°dH<8.5
10< µS/cm<500
6
Installer manual NETZERO