Accessories - Technibel CWX Série Notice D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
5 - FRAME / GRILLE INSTALLATION
• The frame / grille comes in a separate box.
- Code K60N129T for CWX3 and 5
- Code K60N130T for CWX6
- Code K60N131T for CWX8 and 10
• Before installing the facade:
- Remove the retaining screws (1) from the locks (2) on each side
(remember to replace these screws after installation).
- To open the grille (3), turn the two locks (2) in the direction of the
arrow.
- Open the grille (3) 45°.
- Detach the safety cord (4) from the frame (remember to replace it
again after installation).
- Pull the grille inward to remove it from the frame.
• To install the facade:
- Turn the two locking clips (5) downward.
- Attach the frame of the facade (6) to the unit with the two hooks (7)
by lining them up with the locking clips (5).
Note (for CWX 6-8-10 models)
- Observe the position of the facade frame as the hooks are not
the same size. Correctly present them in front of the
corresponding locking clips.
- Check the correct position of the facade frame in relation to
the false ceiling. Adjust the position of the internal unit, as
required.
- Secure the facade frame to the unit using the special screws and
washers (8) provided.
- Fit the grille (3) making sure that the filter (9) is correctly installed.
- Hook the grille safety cord to the frame, close the grille and replace
the lock retaining screws.

6 - ACCESSORIES

VALVE KIT - CODE 70600088 - CWX 3-5
• The valve kit includes:
-
the valve body,
-
2 swivel couplings,
-
actuator (with 230V "On/Off" heating element).
Assembly
A -Valve
directly
connections
Screw the "2 part" portion of the swivel coupling
on the female coupling of the unit. Use a stepped
spanner or a hex wrench. Put sealing compound
or Teflon tape on the threads.
Important: Hold the unit's couplings with a
wrench while tightening to avoid twisting the
tubes inside the unit.
Screw the "1 part" portion of the swivel coupling
onto the valve threads.
Use sealing compound or Teflon on the threads.
on
the
unit's
hydraulic
4
5
6
8
Female couplings
of the unit
Swivel coupling
("2 parts" portion)
Swivel coupling
("1 part" portion)
Valve
3
1
2
GB
5
7
9
3
11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Cwx 3Cwx 5Cwx 6Cwx 8Cwx 10

Table des Matières