6.7 Cleaning

Clean the unit carefully. Remove any dust, foreign substances and dirt possibly deposited during handling.
Use detergents and degreasers.
ATTENTION
Solvents are not allowed.

7 CONNECTING THE UNIT

ATTENTION
Before connecting the unit
correspond to the values shown in the data plate. Voltage tolerance: +/- 10%
compared to nominal value.

7.1 Electric connection

Connect the unit after checking the panel components.
ATTENTION
Connection to the electric line shall be effected applying a suitable safety device
(a circuit breaker or a ground fault interrupter) selected by the installer on the
basis of the line involved and of the absorption indicated on the unit plate.
If a cold room includes more units, each unit shall be provided with its own safety device.
Connect the unit paying attention to the colours of the supply cable wires:
WARNING
Any defective electrical part should be replaced by trained personnel
exclusively.
The electric connection should be effected by qualified personnel.
7.2

Connection to water system

This connection is only necessary if the unit has a water-cooled condenser. It is effected by
following the indications of the tags positioned by the inlet and outlet pipes. Connection pipes should never
be smaller in diameter than those on the unit. A minimum water pressure of 1 bar is required for correct
operation of the unit.

7.3 Connection to humidifier system

Connect humidifier water supply pipe: it is necessary to use a pipe with a diameter of at least
10mm., and pressure in the water circuit must be between 1.5 and 3.0 ATM.
Install a pressure reducer and a filter before water inlet.
WARNING
To prevent water from spilling out of the humidification tray, on first starting set
the pressure reducer to minimum value and close the water cock inside the unit.
a) 230V/1/50-60Hz 3 wires
b) 230V/3/50-60Hz 4 wires
c) 400/3/50 Hz 5 wires
make sure that mains voltage and frequency
Blue = Neutral
Yellow/Green = Ground
Brown = Phase
Blue = Phase
Yellow/Green = Ground
Grey = Phase
Black = Phase
Blue = Neutral
Yellow/Green = Ground
Brown = Phase
Grey = Phase
Black = Phase