11.4. Wiring of main power supply and equipment capacity

Schematic Drawing of Wiring (Example)
[Fig. 11.4.1]
B
3~208–230V
L
, L
, L
1
2
3
B
~208–230V
L, N
A Switch (Breakers for wiring and current leakage)
D Pull box
Thickness of wire for main power supply, on/off capacities
Model
Unit combination
PUHY-HP72THMU-A
PUHY-HP96THMU-A
PUHY-HP144TSHMU-A
PUHY-HP72THMU-A
PUHY-HP72THMU-A
Outdoor unit
PUHY-HP192TSHMU-A
PUHY-HP96THMU-A
PUHY-HP96THMU-A
Indoor unit
1. Use dedicated power supplies for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter.
Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example,
use wiring such as YZW.
6. A switch with at least 3 mm [1/8 in] contact separation in each pole shall be provided by the Air conditioner installation.
Warning:
Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating
or fire may result.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
Some installation sites may require attachment of a ground leakage breaker for the inverter. If a ground leakage breaker is not installed, there is a danger of
electric shock.
Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or fire.
16
, r
2
10 m [32 ft] (0.3 to 1.25 mm
[AWG 22 to 16])
=
2
A
C
Ground
A
E
E
Ground
Ground
Ground
B Breakers for current leakage
E Indoor unit
Minimum wire thickness (mm
Main cable
Branch
13.3 [6]
-
21.2 [4]
-
13.3 [6]
-
13.3 [6]
-
21.2 [4]
-
21.2 [4]
-
0.41 [22]
0.41 [22]
2
[AWG 16] shielded cable and calculate the length of that portion (L
D
E
E
Ground
2
[AWG])
Switch (A)
Breaker
for wiring
Capacity
Fuse
Ground
(NFB) (A)
13.3 [6]
60
60
60
21.2 [4]
75
75
75
13.3 [6]
60
60
60
13.3 [6]
60
60
60
21.2 [4]
75
75
75
21.2 [4]
75
75
75
0.41 [22]
15
15
15
and L
) as within
4
7
C Outdoor unit
Minimum circuit
ampacity
Breaker for current leakage
(MCA) (A)
60A 100mA 0.1sec. or less
53
75A 100mA 0.1sec. or less
71
60A 100mA 0.1sec. or less
53
60A 100mA 0.1sec. or less
53
75A 100mA 0.1sec. or less
71
71
75A 100mA 0.1sec. or less
20A 30mmA 0.1sec. or less
-