ADEUNIS LoRaWAN US902-928 Pulse Guide Utilisateur page 75

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LoRaWAN US902-928 Pulse - Guide utilisateur / User guide version V1.0.0
327
2
Flow threshold (channel B)
328
2
Leak threshold (channel A)
329
2
Leak threshold (channel B)
330
2
Number of daily periods under
the leak threshold (channel A)
331
2
Number of daily periods under
the leak threshold (channel B)
332
1
Scan period for Channel A
tamper input
333
1
Tamper detection threshold
channel A
334
1
Scan period for Channel B
tamper input
335
1
Tamper detection threshold
channel B
Decimal
Default value :0 (deactivated)
Min/max : 0 to 65535
Unit: pulses per hour
Decimal
Default value: 0
Min/max : 0 to 65535
Unit : pulses per hour
Decimal
Default value: 0
Min/max : 0 to 65535
Unit : pulses per hour
Decimal
Default value: 0 (deactivated)
Min/max : 0 to 1440
Unit : none
The multiplication of this register by the period of flow measu-
rement must be less than 24 hours otherwise the product will
be perpetually in alarm.
Decimal
Default value: 0 (deactivated)
Min/max : 0 to 1440
Unit : none
The multiplication of this register by the period of flow measu-
rement must be less than 24 hours otherwise the product will
be perpetually in alarm.
Decimal
Default: 2
Min/Max: 1 to 255
Unit: x10 seconds
Decimal
Default: 3
Min/Max: 1 to 255
Unit: none
Number of positive scans of A-channel tamper before trigge-
ring the tamper alarm
Decimal
Default: 2
Min/Max: 1 to 255
Unit: x10 seconds
Decimal
Default: 3
Min/Max: 1 to 255
Unit: none
Number of positive scans of B-channel tamper before trigge-
ring the tamper alarm
FR
EN
Page
75
of 100

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Arf8230b

Table des Matières