1.5 Connecting the load

Before you connect your appliance(s) to the inverter, always check it's
maximum power consumption. Do not connect appliances to the
inverter needing more than the nominal power rating of the inverter
continuously. Some appliances like motors or pumps, draw large inrush
currents in a start-up situation. In such circumstances, it is possible that
the start-up current exceeds the overcurrent trip level of the inverter. In
this case the output voltage will quickly decrease to limit the output
current of the inverter. If the overcurrent trip level is continuously
exceeded, the inverter will shut down and restart within 18 seconds. In
this case it is advisable to disconnect the appliance from the inverter,
since it requires too much power to be driven by this inverter. Note that
at higher ambient temperature levels, the overload capacity of the
inverter is reduced.
WHEN CONNECTING MORE THAN
ONE APPLIANCE TO THE INVERTER,
IN COMBINATION WITH A
COMPUTER, NOTE THAT IF ONE OF
THE APPLIANCES DRAWS A HIGH
START CURRENT, IT CAN CAUSE
WARNING
YOUR COMPUTER TO REBOOT DUE
TO A SUDDEN VOLTAGE DROP.
NEVER CONNECT THE INVERTER'S
OUTPUT TO THE AC DISTRIBUTION
GRID, SUCH AS YOUR HOUSEHOLD AC
WALL OUTLET. IT WILL DAMAGE
THE INVERTER.
CAUTION