Examples of equipment failures and remedies
Failure
The feed screw does not turn, despite being
signalled as functioning
No air intake despite the fan being signalled
as functioning
Automatic fuel ignition not working
Black smoke in the combustion chamber.
Not combusted fuel in the ash pan.
Flying fuel particles in combustion chamber.
Not combusted fuel in the ash pan.
Set temperature not reached
Smoke coming from the boiler
Leader in pellet boilers
Cause
• no power to gear motor
• wrong wiring of power cables
• the feeder is blocked
• gear motor is faulty
• control module is faulty
• no power to the fan
• fan is faulty
• control module is faulty
• incorrect heating element connection
• heating element hot air outlet blocked
• heating element failure
• flame sensor fouling/failure
• flame sensor opening at the rear grate
wall fouled
• incorrect air volume
• incorrect feed and pause time for specific
power
• incorrect air volume
• incorrect feed and pause time for specific
power
• incorrect boiler size
• sensor failure
• incorrect location of the return water
temperature sensor
• boiler power set too low
• blocked flue
• boiler extension duct blocked
• heat exchanger channels blocked
Twin Bio Luxury Compact NE v01 User Manual – EN 01.19
Remedy
• check control plugs and connectors
• check the connection of the gear motor to
the screw shaft
• check if the feeder duct is not blocked and
that the screw shaft can rotate freely in
the duct
• check fan plugs and cables
(with connectors)
• replace fan
• replace control module
• check heating element plugs and cables
(with connectors)
• clean igniter opening
• high fuel moisture content
• replace heating element
• replace or clean the flame sensor
• clean flame sensor opening
• reduce air volume, check feed and pause
time (burner power too high)
• reduce air volume, check feed and pause
time (burner power too high)
• check correct boiler selection
• sensor check
• check return sensor location
(water circulation required)
• check burner feed and pause times
• clean the ducts and channels
103