Mains
Terminal X100
(left part)
Terminal data
Device sizes I+II:
flexible
with wire end ferrule
Device size III:
flexible
with wire end ferrule
DC bus
Terminal X100
(right part)
Terminal data
Device sizes I+II:
flexible
with wire end ferrule
Device size III:
flexible
with wire end ferrule
EDK94ASH24 DE/EN/FR/ES/IT 3.0
Marking
Description
L1
Connection of the mains phases L1, L2, L3
L2
L3
Connection for the supply-side PE conductor with M5 ring cable
lug
SSP940X100
Max. conductor cross-section
2
[mm
]
[AWG]
2.5
12
10
Marking
Description
+Ug
Alternative option for DC-bus voltage connection (compatible to
9300 series).
-Ug
SSP940X100
Max. conductor cross-section
2
[mm
]
[AWG]
2.5
12
10
Wiring the mounting base
Tightening torque
[Nm]
0.5 ... 0.6
6
1.2 ... 1.5
Tightening torque
[Nm]
0.5 ... 0.6
6
1.2 ... 1.5
Screw drive
[lb-in]
4.5 ... 6.2
PZ0
10.6 ... 13.3
PZ1
Screw drive
[lb-in]
4.5 ... 6.2
PZ0
10.6 ... 13.3
PZ1
47