5. Montage
Mount the unit on a DIN rail or by means of a mounting base. Leave enough
space between the unit and the top and bottom of the control cabinet to enable
air circulation to avoid excessive heating.
Take the internal heating of all units into account when mounting several units
side by side. The environmental conditions must be observed for every unit.
Mounting of the sensors:
Adhere to the mounting instructions of the manufacturer.

6. Electrical connection

Terminal connection

Voltage supply (power)
It is only allowed to operate the unit via one of the possible voltage connections,
i.e. either terminals 7/8, AC/DC or terminals 1/2, 24 V DC.
The supply cable must be protected externally according to the cross-section used
(max. 16 A).
The terminals of the DC supply are directly connected to the terminals of the sen-
sor supply. The SELV criteria must therefore be met for the DC supply (safe extra-
low voltage, circuit galvanically separated from other circuits, not grounded).
Power
AC/DC or
7 8
5
Sensor
supply
6
4
pnp
In 1
10
npn
11
pnp
In 2
12
npn
Reset 1
17
pnp
Reset 2
18
pnp
DC
1 2
3
16
Out 1
15
13
14
24
Out 2
21
19
20
FD-2
MONITOR
page 23