8. Troubleshooting

Diagnosis
1. Oil firing unit
Error signal lamp is not on
Error signal lamp on
2. Motor
Motor does not start
Loud noise caused by running motor
3. Ignition
No generation of ignition sparks
Weak ignition spark
4. Oil pump
Inconsistent oil pressure, loud noise from
operating oil pump, no oil pressure is built up Oil supply not according to the specifications
5. Magnetic valve
Magnetic valve does not open
6. Flame monitoring
Fault shut-down without flame generation
Fault shut-down with flame generation
7. Nozzle
Inconsistent atomisation, high CO and
soot emissions
8. Baffle plate
Baffle plate / burner pipe very contaminated
9. Blower
Blower delivers not enough air
Loud noise during blower operation
Cause
No voltage applied
Boiler temperature controller incorrectly adjusted
Oil firing unit switched to malfunction
Oil firing unit defective
Incorrect wiring of terminal socket
Debug cause for malfunction by LED flashing code
according to chapter 2.6 (only for Siemens LMO 14)
Defective release thermostat of oil pre-heater
Defective capacitor
Stiff bearing
Stiff oil pump
Motor defective
Bearing defective
Oil pump defective
Ignition unit defective
Ignition cable defective
Oil firing unit defective
Insulator defective
Incorrect position of the ignition electrodes
Ignition electrodes severely contaminated
Intake pipe leaking (air entry)
Intake pipe not de-aerated
Oil stop valve closed
Coupling defective
Oil pump filter contaminated
Prefilter contaminated
Oil pump drive defective
Paraffin sedimentation (+4 °C)
Fuel oil viscous (-1 °C)
Coil of the magnetic valve defective
Oil firing unit defective
Extraneous light (photoelectric current >5,5 μA)
Photo conductive cell defective
Photo conductive cell contaminated
Photoelectric current too weak (photoelectric
current < 55 μA)
Defective nozzle
Oil pressure not in compliance with specification
Diaphragm valve defective
(only for burner versions E and F)
Incorrect burner adjustment
Inconsistent atomisation of the nozzle
Nozzle is dripping
Incorrect nozzle type (spraying angle,
spraying characteristics, installation size)
Blower wheel contaminated
Blower wheel damaged
Blower wheel incorrectly positioned
Blower wheel damaged
Air flap incorrectly installed
Rectification
Check wiring
Adjust
Remedy malfunction
Replace
Check wiring
Check oil pre-heater
Remedy debugged malfunction according
to error diagnosis point 2 ... 10
Replace oil pre-heater
Replace capacitor
Replace motor
Replace oil pump
Replace motor
Replace motor
Replace oil pump
Replace ignition unit
Replace ignition cable
Replace oil firing unit
Replace ignition electrodes
Position ignition electrodes
Clean ignition electrodes
Check oil supply (see chapter 3.5)
Check oil supply (see chapter 3.5)
De-aerate intake pipe
Open stop valve
Replace coupling
Clean oil pump filter
Clean/replace prefilter
Replace oil pump
Install at a frost-free place
Install at a frost-free place
Replace coil of the magnetic valve
Replace oil firing unit
Remove extraneous light
Replace photo conductive cell
Clean photo conductive cell
Reset burner
Replace nozzle
Adjust oil pressure
Replace diaphragm valve
Adjust burner according to chapter 3.8
and chapter 5 (basic adjustment table).
Replace nozzle and diaphragm valve, if
necessary (only for burner versions E and F)
Replace diaphragm valve (only for burner
version E and F)
Insert nozzle according to specification
(see chapter 4 and chapter 5)
Clean blower wheel
Replace blower wheel
Correctly position blower wheel
Replace blower wheel
Correctly install air flap