BRIEF DESCRIPTION OF THE UNIT

Casings of air handling units are made of galvanized steel sheets, which are powder painted. Mineral wool is
used for thermal insulation and sound attenuation. REGO 600 unit cover panels are 45 mm thick.
The air handling units are intended for ventilation of medium-sized spaces (eg. single family houses,
offices, etc.), having operating ambient temperature and relative humidity. As standard, the unit is designed for
indoor placement. In cold, wet rooms possible icing or condensation on the housing inside and outside. The
operating temperature range for the unit is -30 °C ... 40 °C, outdoor air temperature. The air handling unit is
not to be used to transport solid particles, even not in areas where there is a risk of explosive gases. Extracted
indoor air temperature +10 – +40 °C, relative humidity (non-condensing) 20–80 %.
REGO is equipped with a rotary heat exchanger, air filters, an electric or water heater, fans and automation
control system, to ensure safe and efficient operation of the unit.
Before you open the door, the unit must be switched off and the fans must have been given time to stop (up
to 3 minutes).
The unit contains heating elements that must not be touched when they are hot.
We recommend to leave air handling unit in working mode (minimum 20 percent of power) during the first
operation year. Due to moisture in building constructions, condensation may occur inside and outside the air
handling unit. Continuous operation of the equipment will significantly reduce the risk of condensation.
We recommend to leave air handling unit in working mode (minimum 20 percent of power) during the first
operation year. Due to moisture in building constructions, condensation may occur inside and outside the air
handling unit. Continuous operation of the equipment will significantly reduce the risk of condensation.
To maintain a good indoor climate, comply with regulations and, to avoid condensation damage, the unit must
never be stopped apart from during service/maintenance or in connection with an accident.
If the unit is placed in spaces with high humidity, condensation might occur on the surface of the unit when
outdoor temperatures are very low.
1. Rotary heat exchanger
2. Air heater (electric or hot water)
3. Supply air filter
4. Exhaust air filter
5. Supply fan
6. Exhaust fan
* R – right inspection side.
** Ducted water heater.
UAB AMALVA we reserve the right to make changes without prior notice
REGO Horizontal Air Handling Units Schemes
3
6
1
4
2
5
Outdoor intake
Supply air
Extract indoor
Exhaust air