Télécharger Imprimer la page

Siemens RVL479 Instructions D'installation page 28

Masquer les pouces Voir aussi pour RVL479:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 34
Parameter list
Line
Function, display
Block "Space heating"
en
61
Heating limit for
NORMAL heating
(ECO day)
62
Heating limit for
REDUCED heating
(ECO night)
63
Building time con-
stant
64
Quick setback
65
Room temperature
source
66
Type of optimization
67
Maximum heating-
up time
Building Technologies
Factory setting
Setting
(Range)
17.0 °C
(--.- / −5.0...+25.0)
...................
5.0 °C
(--.- / −5.0...+25.0)
...................
20 h
(0...50)
......................
1
(0 / 1)
.........................
A
(0 / 1 / 2 / 3 / A)
.........................
0
(0 / 1)
.........................
00:00 h
(00:00...42:00)
......................
74 319 0620 0 a
Explanations, notes and tips
Setting --.- = function disabled
°C
Setting --.- = function disabled
°C
Light = 10 h
h
Medium = 25 h
Heavy = 50 h
0 = no quick setback
1 = quick setback
0 = no room temperature sen-
sor present
1 = room unit at terminal A6
2 = room temperature sensor at
terminal B5
3 = mean value of the two units
at terminals A6 and B5
A = automatic selection
0 = optimization with room
model
1 = optimization with room
temperature sensor / room
unit
(setting 0 only allows optimum
start control)
Maximum forward shift for
h
switching on before start of
occupancy
Setting 00:00 = optimization of
switching on disabled
17.04.2008
28/152

Publicité

loading