Increase the temperature measured by the ambient temperature sensor
by 2°C by pressing
.
In our example the measured temperature by the sensor goes
from 21°C to 23°C.
To validate the new value press
3 times.
The reset to zero of the sensor calibration
To put the value of the correction to "0", do the following :
1- When the temperature measured by the sensor appears, press
or
for at least 3 seconds.
2- To save and move automatically to the next setting press
exit the Expert settings, press
Important:
These changes should be performed by a qualified
staff, it should be performed in production or on site during the
first installation

INTERNAL TEMPERATURE MONITORING

An integrated overheating safety is present on our blower. It is acti-
vated when an internal temperature limit is reached: the blower and its
controller will stop immediately.
The maximum setting is preset to 65°C. You can adjust from 60°C to
90°C by intervals of 5°C.
Press
or
then save by pressing
If you do not want to change it, press
tically to set the next setting.
To exit the Expert settings, press
M16MI325 A03_06/18
. To exit the Expert settings, press
3 sec.
3 times.
.
: the device changes automa-
1
2
3 times.

HYSTERESIS ADJUSTMENT

Important:
These changes should be performed by a qualified
staff.
The hysteresis used by the controller can be adjusted.
The hysteresis setting is preset to 1°C. You can adjust from 0.5°C to 3°C
by intervals of 0.5°C.
Press
or
then save by pressing
If you do not want to change it, press
tically to set the next setting.
To exit the Expert settings, press

RESTORING FACTORY SETTINGS

If the PIN code protection is disabled, the user, installer and expert set-
tings are re-initialized:
1- From the internal temperature monitoring setting, press
appears on the display.
. To
NO
2-
appears. Press
yes
= Factory settings reset
NO
= Factory settings not reset
3- Press the key
for 5 seconds. The device returns to its initial confi-
guration and goes back automatically to the Auto mode.
.
: the device changes automa-
1
3 times.
YES
or
to select
.
2
rest
.
5 sec.