Télécharger Imprimer la page

Honeywell VisionPRO IAQ Guide D'installation page 7

Masquer les pouces Voir aussi pour VisionPRO IAQ:

Publicité

Les langues disponibles

Les langues disponibles

VisionPRO
®
IAQ
Installer setup
Setup functions
0502
Furnace filter
alert options
0510
Humidifier pad
change alert
0520
UV lamp change
alert
0530
Adaptive Intelligent
Recovery
0540
Program periods
0570
Non-compressor
off time (min.)
0580
Compressor off
time (min.)
0600
Heat temperature
range stop
0610
Cool temperature
range stop
0620
Non-compressor
on time (min.)
0630
Compressor on
time (min.)
0640
Clock format
0650
Extended fan
timer (heat)
0660
Extended fan
timer (cool)
0670
Keypad lock
0680
Heat temperature
control
0690
Cool temperature
control
(English: Page 4 • Français: Page 10 • Español: Página 16)
Settings & Options
0 Timer counts Heat & Cool run time
1 Timer counts Cool run time only
E Auto Discover
0 Off
1 90 calendar days (about 30 days run time)
2 180 calendar days (about 60 days run time)
3 365 calendar days (about 90 days run time)
E Auto Discover
0 Off
1 365 calendar days (1 year)
2 730 calendar days (2 years)
1 On
**
0 Off
4 4 program periods (Wake, Leave, Return, Sleep)
2 2 program periods (Wake, Sleep)
0 Off
[Other options: 1 to 5 minutes]
5 5 minute compressor off time
[Other options: 0 to 4 minutes]
90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40 to 90°F (4°C to 32°C)]
60 Min. cool temperature setting is 60°F (15°C)
[Other options: 60-99°F (15°C to 37°C)]
0 Off
[Other options: 1 to 15 minutes]
0 Off
[Other options: 1 to 15 minutes]
12 12-hour time (i.e., "3:30 pm")
24 24-hour time (i.e., "15:30")
0 Off
[Other options: Fan runs for 30, 60, 90 or 120 seconds after
call for heating ends]
0 Off
[Other options: Fan runs for 30, 60, 90 or 120 seconds after
call for cooling ends]
0 Keypad unlocked (fully functional)
1 Partially locked (access to temperature settings only)
2 Fully locked
2 Standard temperature control (recommended)
1 Choose if room is warmer than set temperature
3 Choose if room does not reach set temperature
2 Standard temperature control (recommended)
1 Choose if room is cooler than set temperature
3 Choose if room does not reach set temperature
(factory default in bold)
**
**