Exemples De Signal De Sortie En Régimes Périodique Et Permanent - Rockwell Automation ControlLogix 1756-HSC Manuel Utilisateur

Module compteur rapide
Table des Matières

Publicité

Exemples de signal de
sortie en régimes
périodique et permanent
Outputs in Period Rate and Continuous Rate with Scaler = 1
50 Hz at Z-Input
50% Duty Cycle
Scaler Tag= 1
Counter Times
Width of Pulse
4 MHz Count in Present Value Tag = 40,000
Output State in Period Rate
Scaler Tag = 1
Output OnValue Tag = 20,000
Output OffValue Tag = 80,001
Output State in Continuous Rate
4 MHz Count
= 20,000
Scaler Tag = 1
Output OnValue = 20,000
Output OffValue = 80,001
Outputs in Period Rate and Continuous Rate with Scaler = 2
50 Hz at Z-Input
50% Duty Cycle
Scaler Tag = 2
What the Counter
Sees Internally With
Scaler Tag = 2
Counter Times
Width of Pulse
4 MHz = 80,000
Output State in Period Rate
Scaler Tag = 2
Output OnValue Tag = 20,000
Output OffValue Tag = 80,001
Output State in Continuous Rate
4 MHz Count
= 20,000
Scaler Tag = 2
Output OnValue = 20,000
Output OffValue = 80,001
Ces différents signaux carrés illustrent les différences entre les modes de
fonctionnement Régime périodique et Régime permanent. Toutes ces ondes
carrées ont été générées en appliquant un signal de 50 Hz à la borne d'entrée Z
d'un compteur configuré soit pour le Régime périodique, soit pour le Régime
permanent. La configuration des sorties est la même dans tous les cas, avec
une valeur d'activation de 20 000 et de désactivation de 80 001. Seule la valeur
d'échelle de comptage varie pour montrer les différences de fonctionnement
entre les deux modes.
Counter
Idle
4 MHz Count = 40,000
4 MHz Count
= 40,000
Counter Idle
4 MHz Count = 80,000
4 MHz Count
= 80,000
Publication Rockwell Automation 1756-UM007E-FR-P - Août 2021