Quick Guide

1.8 General Technical Data

Protection and features
Electronic motor thermal protection against overload.
Temperature monitoring of the heat sink ensures that the frequency converter trips if there is overtemperature.
The frequency converter is protected against short circuits between motor terminals U, V, W.
When a motor phase is missing, the frequency converter trips and issues an alarm.
When a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the DC-link voltage ensures that the frequency converter trips when the DC-link voltage is too low
or too high.
The frequency converter is protected against ground faults on motor terminals U, V, W.
Mains supply (L1/L, L2, L3/N)
Supply voltage
Supply voltage
Supply frequency
Maximum imbalance temporary between mains phases
True power factor
Displacement power factor (cosφ) near unity
Switching on input supply L1/L, L2, L3/N (power-ups)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 240/480 V
maximum.
Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
Cable length and cross-section
Maximum motor cable length, shielded/armored (EMC-correct installation)
Maximum motor cable length, unshielded/unarmored
Maximum cross-section to motor, mains
Connection to load sharing/brake (M1, M2, M3)
Maximum cross-section to load sharing/brake (M4, M5)
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Maximum cross-section to control terminals, cable with enclosed core
Minimum cross-section to control terminals
1) See chapter 1.7 Specifications for more information.
MG02BC4P
Quick Guide•Kurzanleitung•Guide rapide•Guía rápida•Guia Rápido•Краткое
руководство
1)
Danfoss A/S © 10/2017 All rights reserved.
200–240 V ±10%
380–480 V ±10%
3.0% of rated supply voltage
≥0.4 nominal at rated load
Maximum 2 times/minute
Overvoltage category III/pollution degree 2
0–100% of supply voltage
+
0–200 Hz (VVC
), 0–400 Hz (u/f )
6.3 mm insulated Faston plugs
16 mm
2
1.5 mm
/16 AWG (2x0.75 mm
1 mm
0.5 mm
0.25 mm
1
1
50/60 Hz
(>0.98)
Unlimited
0.05–3600 s
15 m (49 ft)
50 m (164 ft)
2
/6 AWG
2
)
2
/18 AWG
2
/20 AWG
2
(24 AWG)
27