Quick Guide
Relay output
Programmable relay output
Relay 01 terminal number
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Minimum terminal load on 01–03 (NC), 01–02 (NO)
Environment according to EN 60664-1
1) IEC 60947 part 4 and 5
Control card, 10 V DC output
Terminal number
Output voltage
Maximum load
NOTICE
All inputs, outputs, circuits, DC supplies, and relay contacts are galvanically isolated from the supply voltage (PELV) and
other high-voltage terminals.
Surroundings
Enclosure protection rating
Enclosure kit available
Vibration test
Maximum relative humidity
Aggressive environment (IEC 60721-3-3), coated
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
1)
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Safety standards
EMC standards, Emission
EMC standards, Immunity
Energy efficiency class
1) Refer to chapter 1.9 Special Conditions for:
Derating for high ambient temperature.
Derating for high altitude.
2) Determined according to EN 50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.
MG02BC4P
Quick Guide•Kurzanleitung•Guide rapide•Guía rápida•Guia Rápido•Краткое
руководство
1)
on 01–02 (NO) (Resistive load)
1)
on 01–02 (NO) (Inductive load @ cosφ 0.4)
1)
on 01–02 (NO) (Resistive load)
1)
on 01–02 (NO) (Inductive load)
1)
on 01–03 (NC) (Resistive load)
1)
on 01–03 (NC) (Inductive load @ cosφ 0.4)
1)
on 01–03 (NC) (Resistive load)
5%–95 % (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
1)
1)
Danfoss A/S © 10/2017 All rights reserved.
24 V DC 10 mA, 24 V AC 20 mA
Overvoltage category III/pollution degree 2
-25 to +65/70 °C (-13 to + 149/158 °F)
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
1
01–03 (break), 01–02 (make)
250 V AC, 2 A
250 V AC, 0.2 A
30 V DC, 2 A
24 V DC, 0.1 A
250 V AC, 2 A
250 V AC, 0.2 A
30 V DC, 2 A
50
10.5 V ±0.5 V
25 mA
IP20
IP21, TYPE 1
1.0 g
class 3C3
Maximum 40 °C (104 °F)
0 °C (32 °F)
-10 °C (14 °F)
1000 m (3280 ft)
3000 m (9842 ft)
EN/IEC 61800-5-1, UL 508C
IE2
29
1
1