Connect Condensate Drain - Helios KWL Yoga 400 Notice De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Instructions
ACHTUNG
Decentralised ventilation unit – KWL
1. Loosen and remove screws (12 pcs) on the bottom of the unit (see Fig. 23).
2. Carefully open the cover by pushing the securing tabs (see Fig. 24).
4 .3

Connect condensate drain

The odour trap must be professionally connected to the condensate connector and sealed.
We recommend flooding each odour trap with water and checking its functionality.
In order to drain the condensate safely, a tube with min. 100 mm length must be provided between the condensate
connector and siphon.
An improperly installed odour trap can cause damage to the building and unit.
We recommend the ball siphon KWL-KS (Helios accessories) or the ball siphon for wall installation KWL-KS WE (Helios
accessories). Follow the corresponding installation and operating instructions for the ball siphon!
®
Yoga / KWL
push
15
®
Yoga Style
18 mm
Fig .23
Fig .24
Fig .25