Operating Range - Rheem Classic Plus Série Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2. 4. 3. Connectable indoor unit capacity type (Outdoor unit: 18 type)
Power source
Power cable
208/230 V ~ 60 Hz
Connection cable
OUTDOOR UNIT
Refrigerant pipe
The total capacity of the indoor units connected must be between 14,000 and 21,000
BTU.
Connection patterns are restricted. Normal operation is not guaranteed if connected
pattern in the combination not listed below. The product may be damaged. Surely con-
nect in accordance with the combination in the following connection pattern.
• To install an indoor unit, refer to the installation instruction sheet included with the
indoor unit.
Indoor unit connection pattern
Indoor unit
1
1
7,000
2
9,000
3
12,000
4
9,000
5
12,000
Outdoor port
Standard port size [in. (mm)]
B
1/4 (6.35) / 3/8 (9.52)
A
1/4 (6.35) / 3/8 (9.52)
UNIT B
7-12
b
UNIT A
a
7-12
INDOOR UNITS
CAUTION
2
7,000
7,000
7,000
9,000
9,000
Connectable model name
7 – 12
7 – 12
UNIT B ø1/4 in., ø3/8 in. (ø6.35mm, ø9.52mm)
UNIT A ø1/4 in., ø3/8 in. (ø6.35mm, ø9.52mm)
2. 4. 4. Limitation of refrigerant piping length (18 type)
The total maximum pipe lengths and height difference of this product are shown in the
table.
If the units are further apart than this, correct operation cannot be guaranteed.
Total max. length (a+b)
H1
Max. length for each indoor unit
(a or b)
H2
Max. height difference between
outdoor unit and each indoor unit
(H1)
Max. height difference between
indoor units (H2)
H1
Min. length for each indoor unit
(a or b)
Total min. length (a+b)
*1 If the total piping is longer than 98 ft (30 m), additional refrigerant charging is neces-
)
sary. (For more information, refer to "6.2 Additional charging".)
2. 4. 5. Selecting pipe sizes
The diameters of the connection pipes differ according to the capacity of the indoor unit.
Refer to the following table for the proper diameters of the connection pipes between the
indoor and outdoor units.
Capacity of indoor
unit
7 – 12
15 – 18
Operation cannot be guaranteed if the correct combination of pipes, valves, etc., is not
used to connect the indoor and outdoor units.
2. 4. 6. Heat insulation around connection pipes requirements
Install heat insulation around both the gas and liquid pipes.
Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 248 °F. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70%, install heat insulation around the refrigerant piping. If the
expected humidity level is 70-80%, use heat insulation that is 19/32 in. or thicker and if
the expected humidity exceeds 80%, use heat insulation that is 25/32 in. or thicker.
If heat insulation is used that is not as thick as specifi ed, condensation may form on
the surface of the insulation. In addition, use heat insulation with heat conductivity of
0.045 W/(m·K) or less (at 68 °F).
Connect the connection pipes according to "4.1. Pipe connection" in this installation manu-
al.

2. 4. 7. Operating range

Temperature
Maximum
Cooling
Minimum
Maximum
Heating
Minimum
CAUTION
164 ft (50 m)*
82 ft (25 m)
49 ft (15 m)
33 ft (10 m)
16 ft (5 m)
49 ft (15 m)
Gas pipe size
Liquid pipe size
(thickness)
(thickness)
[in. (mm)]
[in. (mm)]
ø3/8 (1/16) [9.52 (0.8)]
ø1/4 (1/16) [6.35 (0.8)]
ø1/2 (1/16) [12.70 (0.8)]
ø1/4 (1/16) [6.35 (0.8)]
CAUTION
CAUTION
Indoor air intake
Outdoor air intake
90 °F DB
65 °F DB
88 °F DB or less
60 °F DB or less
Indoor humidity about 80% or less
1
115 °F DB
14 °F DB
75 °F DB
5 °F DB
En-4

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Romh24afxzj

Table des Matières