Press the contextual buttons 1 and 2 to increase the maximum power of all modules.
To deactivate the CASCADE TEST mode, press the contextual button 3.
The CASCADE TEST mode is disabled automatically in any case after 15 minutes.
After activating test mode, to exit the TEST make sure to deactivate the function, only by pressing the contex-
A
tual button "Stop Test".
DO NOT TURN OFF THE BOILER ELECTRICALLY DURING THE TEST.
If that happens, when the power is switched on again the system does not recognise deactivation of the TEST,
and starts working as though still in TEST mode and not as in a normal heating demand.

TECHNICAL MENU

ONLY QUALIFIED PERSONNEL CAN ACCESS THE SERVICE MENU AND MODIFY PARAMETERS.
The Technical Menu can only be accessed after entering the code 4 1 8. It is valid for 15 minutes.
Configuration - Parameters Menu
There are 16 parameters, indicated by the letter "b", which are not modifiable from Remote Timer Control.
Table 5- Parameters - Configuration
Parameter
Description
b01
Gas type selection
b02
Boiler type selection
b03
System water pressure protection selection
b04
Fan max. frequency in DHW
b05
Fan max. frequency in heating
b06
Fan min. frequency in DHW/heating
b07
Fan min. Frequency Offset
b08
Variable output Relay operation selection
b09
Post-Ventilation
b10
Boiler room pre-ventilation
b11
Boiler room post-ventilation
b12
Fume sensor
b13
Not implemented
b14
Fumes Max Temperature
b15
Fan type selection
b16
Pump antiblock operation time
Notes
1. Parameters with more than one description vary their function and/or range in relation to the setting of the parameter given in brackets.
2. Parameters with more than one description are reset to the default value if the parameter given in brackets is modified.
EN
Range
Natural Gas/LPG
1-9
0=Pressure switch
1=Flow switch 1 sec.
2=Flow switch 3 sec.
3=Flow switch 5 sec.
4=Flow switch 10 sec.
5=Pressure transducer
0-255 Hz
0-255 Hz
0-255 Hz
0-255 Hz
0=Burner lit
1=Legionella pump
2=Boiler room ventilation
3=Motor-operated shutoff valve
0-120 seconds
1-15 minutes
1-15 minutes
OFF = Deactivated,
ON = Enabled
--
0-125°C
--
0-20 seconds
cod. 3541T170 - Rev. 00 - 09/2019
FORCE B
FORCE B
FORCE B
80
120
150
Natural
Natural
Natural
Gas
Gas
Gas
7
7
7
0
0
0
190
225
240
190
225
240
50
45
50
40
40
40
0
0
0
30
30
30
1
1
1
1
1
1
ON
ON
ON
--
--
--
110
110
110
--
--
--
5
5
5