ATLAS D ECO COND UNIT

4.4 Technical data table

Data
Number of elements
Max. heating capacity
Min. heating capacity
Max. heat output in heating (80/60)
Min. heat output in heating (80/60)
Max. heat output in heating (50/30)
Min. heat output in heating (50/30)
Efficiency Pmax (80-60°C)
Efficiency Pmin (80-60°C)
Efficiency Pmax (50-30°C)
Efficiency Pmin (50-30°C)
Efficiency 30%
Max. working pressure in heating
Min. working pressure in heating
Max. heating temperature
Heating water content
Heating expansion vessel capacity
Heating expansion vessel precharge pressure
Protection rating
Power supply voltage
Electrical power input
Empty weight
Combustion chamber length
Combustion chamber diameter
Pressure loss on fume side
MODEL: ATLAS D ECO 34 COND UNIT - (0JHW3YWA)
MODEL: ATLAS D ECO 45 COND UNIT - (0JHW4YWA)
Trademark: FERROLI
Condensing boiler: YES
Low-temperature boiler (**): YES
B1 Boiler: NO
Combination heater: NO
Cogeneration space heater: NO
Item
Seasonal space heating energy efficiency class (from A+++ to D)
Rated heat output
Seasonal space heating energy efficiency
Useful heat out put
Useful heat output at rated heat output and high-temperature regime (*)
Useful heat output at 30% of rated heat output and low-temperature regime (**)
Useful efficiency
Useful efficiency at rated heat output and high-temperature regime (*)
Useful efficiency at 30% of rated heat output and low-temperature regime (**)
Auxiliary electricity consumption
At full load
At part load
In standby mode
Other items
Standby heat loss
Ignition burner power consumption
Annual energy consumption
Sound power level
Emissions of nitrogen oxides
(*) High-temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30°C, for low-temperature boilers 37°C and for other heaters 50°C return temperature (at heater inlet).
Unit
no.
kW
kW
kW
kW
kW
kW
%
%
%
%
%
bar
bar
°C
liters
liters
bar
IP
V/Hz
W
kg
mm
mm
mbar
ErP product fiche
(
)
cod. 3541Q464 - Rev. 00 - 12/2021
ATLAS D ECO 34 COND UNIT
ATLAS D ECO 45 COND UNIT
3
33.0
16.3
32
16
33.8
17.0
97.2
97.8
102.6
103.7
103.5
3
0.8
100
21
10
1
X0D
230/50
224
177
350
300
0.12
Symbol
Unit
Pn
kW
s
%
P4
kW
P1
kW
%
4
1
%
elmax
kW
elmin
kW
PSB
kW
Pstby
kW
Pign
kW
QHE
GJ
LWA
dB
NOx
mg/kWh
4
43.5
(Q)
30.9
(Q)
42
(P)
30
(P)
44.5
(P)
31.7
(P)
96.6
97.3
102.3
102.8
102.8
3
(PMS)
0.8
100
(tmax)
26
10
1
X0D
230/50
228
216
450
300
0.18
0JHW3YWA - 0JHW4YWA
Value
Value
A
A
32
42
91
90
32,1
42,0
9,6
12,6
91,3
90,7
97,2
96,5
0,200
0,230
0,105
0,118
0,003
0,003
0,105
0,120
0,000
0,000
102
133
62
63
91
89
47
EN