Condensate Drain Connection - Ferroli FORCE B Instructions D'utilisation, D'installation Et D'entretien

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

FORCE B

2.7 Condensate drain connection

IMPORTANT
The boiler has a trap to drain condensate. Proceed as follows for assembly.
1. Fill the trap with water through the fume evacuation duct.
2. Connect the boiler discharge pipe and condensate drain (A - fig. 57) to a disposal system.
Drains connected to the drainage system must be resistant to acidic condensate.
If the condensate drain is not connected to the waste water discharge system, a neutralizer must be installed.
B
ATTENTION: THE UNIT MUST NEVER BE OPERATED WITH THE TRAP
EMPTY!
OTHERWISE THERE IS A DANGER OF SUFFOCATION DUE TO THE EMIS-
SION OF COMBUSTION FUMES.
THE CONDENSATE DRAIN MUST BE CONNECTED TO THE DRAINAGE SYS-
TEM IN SUCH A WAY THAT THE LIQUID CONTAINED CANNOT FREEZE.
EN
fig. 57- Condensate drain connection
cod. 3541T170 - Rev. 00 - 09/2019
A
153

Publicité

Table des Matières
loading

Table des Matières