IF THE ABOVE INSTRUCTIONS ARE NOT OBSERVED THERE MAY BE RISK
OF SUFFOCATION OR POISONING DUE TO GAS OR FUMES ESCAPING;
DANGER OF FIRE OR EXPLOSION. ALSO, THERE MAY BE A RISK OF ELEC-
TRIC SHOCK OR FLOODING THE ROOM.
Checks during operation
Turn the unit on as described in sec. 1.3.
Make sure the fuel circuit and water systems are tight.
Check the efficiency of the flue and air-fume ducts while the boiler is working.
Check the correct tightness and functionality of the condensate elimination system and trap.
Make sure the water is circulating properly between the boiler and the systems.
Make sure the gas valve modulates correctly in the heating and domestic hot water production phases.
Check proper boiler lighting by doing several tests, turning it on and off with the room thermostat or remote control.
Using a combustion analyser connected to the boiler fume outlet, check that the CO
boiler operating at max. and min. output, corresponds to that given in the technical data table for the corresponding
type of gas.
Make sure the fuel consumption indicated on the meter matches that given in the technical data table on sec. 4.4.
Check the correct programming of the parameters and carry out any necessary customization (compensation curve,
power, temperatures, etc.).

3.3 Maintenance

IMPORTANT
B
ALL MAINTENANCE WORK AND REPLACEMENTS MUST BE CARRIED OUT
BY SKILLED QUALIFIED PERSONNEL.
Before carrying out any operation inside the boiler, disconnect the power
and close the gas cock upstream. Otherwise there may be a danger of explo-
sion, electric shock, suffocation or poisoning.
Periodical check
To ensure lasting proper operation of the unit, it is necessary to have an annual inspection carried out by qualified per-
sonnel, providing for the following:
Heat exchanger check and cleaning with suitable products if dirty or clogged.
The exchanger can be cleaned only when its temperature is under 40°C.
Clean only with suitable products approved by the manufacturer, e.g.:
ALU CLEANGEL
BIO HALL LIQUID
Check and cleaning (if necessary) of burner (do not use chemical products or wire brushes).
Check and cleaning of electrodes, which must be free of deposits and properly positioned.
Check of gaskets and seals (burner, sealed chamber, etc.).
Check and cleaning of sludge remover filters and system filters.
Check, cleaning and filling of condensate drain traps.
Check of wiring, contacts, electrical actuators.
Check and cleaning of generator air inlets and boiler room air intakes.
Check and cleaning of fume evacuation duct-manifold-flue system.
Check of expansion tank and precharge.
Check of correct and stable system water pressure, ensuring conformity with the required working pressure.
B
The use of automatic filling systems for reinstatement of operating conditions
must provide for adequate treatment of the water (ref. "System water characte-
ristics" on page 137)
check of heating system water chemical and physical parameters (ref. "System water characteristics" on page 137)
water and gas system tightness check
check of correct and stable gas supply pressure to the plant (20 mbar for operation with natural gas); any fluctuations
or pressure drops below the declared value can create malfunctioning and stops with need for manual resetting.
check of correct burner ignition and operation of control and safety devices (gas valve, flow meter, thermostats, etc.)
160
cod. 3541T170 - Rev. 00 - 09/2019
FORCE B
content in the fumes, with the
2
EN