Installation; General Instructions; Place Of Installation; Plumbing Connections - Ferroli FORCE B Instructions D'utilisation, D'installation Et D'entretien

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

2. Installation

2.1 General Instructions

BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH
ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE
PRESCRIPTIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP.

2.2 Place of installation

The generator must be installed in a suitable room with ventilation openings towards the outside in conformity with cu-
rrent regulations. If there are several burners or exhausters that can work together in the same room, the ventilation
openings must be sized for simultaneous operation of all the units. The place of installation must be free of flammable
materials or objects, corrosive gases, powders or volatile substances. The room must be dry and not exposed to rain,
snow or frost.
During installation it is necessary to provide the space for normal maintenance activities.
A

2.3 Plumbing connections

Important
The heating capacity of the unit must be previously established by calculating the building's heat requirement according
to current regulations. The system must be provided with all the components for correct and regular operation. In par-
ticular, provide for all the protection and safety devices required by current regulations for the complete modular gene-
rator. They must be installed on the hot water circuit delivery piping, immediately after the last module, within a distance
of not more than 0.5 m. and with no shutoff devices in between. The unit is not supplied with an expansion tank; its
connection must therefore be carried out by the Installer.
Do not use the water system pipes to earth electrical appliances.
Before installation, flush all the pipes of the system thoroughly to remove any residuals or impurities that could affect
proper operation of the unit.
B
Also, a filter must be installed on the system return piping to prevent impurities or
sludge from the system clogging and damaging the heat generators.
The filter must be installed when replacing generators in existing systems. The ma-
nufacturer declines any liability for damage caused to the generator by failure to
install or inadequate installation of this filter.
Carry out the relevant connections according to the diagram in sec. 4.1 and the symbols on the unit.
134
cod. 3541T170 - Rev. 00 - 09/2019
FORCE B
EN

Publicité

Table des Matières
loading

Table des Matières