Fault code
Fault
Possible cause
F35
Faulty mains frequency
Electric mains trouble
Insufficient system pres-
sure or circulation
Flowswitch or pressure
Circulating pump not
F37
switch contact open
working
Wrong card parameter
setting
Flowswitch contact
Flowswitch dirty or
F38
blocked closed
blocked
Probe damaged or wiring
shorted
F39
External probe fault
Probe disconnected after
activating the sliding tem-
perature
Delivery sensor discon-
A41
Sensor positioning
nected from the pipe
A42
Heating sensor fault
Sensor damaged
F42
Heating sensor fault
Sensor damaged
Sensor damaged
Cascade temperature
F50
Wiring shorted
sensor fault
Wiring disconnected
Controller DBM12 inter-
A61
Controller DBM12 fault
nal error
No communication
Controller not connected
A62
between controller and
Valve damaged
gas valve
A63
A64
Controller DBM12 inter-
Controller DBM12 fault
A65
nal error
F66

5. TECHNICAL DATA AND CHARACTERISTICS

Key of figures cap. 5
7
Gas inlet
10
System delivery
11
System return
16
Fan
22
Main burner
29
Fume outlet manifold
32
Heating circulating pump (not supplied)
36
Automatic air vent
38
Flow switch
44
Gas valve
72
Room thermostat (not supplied)
72b
Second room thermostat (not supplied)
81
Ignition electrode
82
Detection electrode
95
Diverter valve (not supplied)
A = Heating phase
B = DHW phase
C = Neutral
NOTE: For valves with 2 wires and spring return, use the connections B and C
98
Switch
114
Water pressure switch
130
DHW circulating pump (not supplied)
138
External probe (not supplied)
139
Remote timer control (not supplied)
154
Condensate drain pipe
155
Hot water tank temperature probe (not supplied)
186
Return sensor
191
Fume temperature sensor
193
Trap
196
Condensate tray
215
Air inlet reducer
220
Ignition card
256
Modulating heating circulating pump signal
278
Double sensor (Safety + Heating)
298
Cascade temperature sensor (not supplied)
299
Input 0-10 Vdc
300
Burner lit contact (voltage-free contact)
301
Fault contact (voltage-free contact)
302
Remote reset input (230 Volt)
306
Heating system circulating pump (not supplied)
307
Heating system second circulating pump (not supplied)
345
Exchanger safety thermostat
52
EN
ENERGY TOP W 70 - W 80 - W 125
All manuals and user guides at all-guides.com

5.1 Dimensions and connections

Cure
Check the electrical system
Check the system water pressure or for
air in the system
Check the circulating pump
Check the card parameter and modify it if
necessary
Clean the flowswitch or replace it if nec-
essary
Check the wiring or replace the sensor
Reconnect the external probe or disable
the sliding temperature
Check the correct positioning and opera-
tion of the heating sensor
Replace the sensor
Replace the sensor
Check the wiring or replace the sensor
Check the earth connection and replace
the controller if necessary.
Connect the controller to the gas valve
Replace the valve
Check the earth connection and replace
the controller if necessary.
1
ENERGY TOP W 70 - W 80
ENERGY TOP W 125
1 =
3 =
5 =
cod. 3540S806 - Rev. 00 - 09/2013
Ø 80
Ø 80
445
222
120
84
278
A
20
3
5
fig. 37 - Dimensions and connections
Heating system delivery - 1" 1/2 F
Gas inlet - 1" M
Heating system return - 1" 1/2 F
49
102
440
A
65
63